- PCME QAL 181 MANUAL: 55 -
Note 2:
Averaging is done using a walking window filter. This means the average
values used to generate alarms may differ from the averaged logged data which uses
simple averaging.
Note 3:
The averaging filter is reset at power up and after making sensor setting
adjustments. During the initial period the reading will be an average of a shorter
period than the averaging time. This may result in unwanted alarms.
Note 4:
To disable any of the alarm levels set the value to 0.00.
6.8
Set Time / Date
Select ‘Setup’ display
Menu route:
Time / Date
The following screen is displayed.
Figure 5-4 Time / Date Configuration
Changing the time / date may result in loss of logged data.
The system does not automatically change the time for daylight saving hours (clocks
forward or back).
Default setting is Greenwich Mean Time.
Use the cursor keys to highlight the parameter to be changed and the enter key to change the
value. To save the changes and return to the main menu select the Clock icon on the top left of
the screen.
If the time is set back the Controller will not log new data until the time has passed the latest
timestamp in the log. (i.e. if the time is put back 1 hour from 10.00 to 09.00 the Controller will
not log data until the time reaches 10.00. If the time is put back by more than 24 hours the
Controller will clear all logs and start logging again immediately.
WARNING Time adjustments
may lose logged data!
09
36
03
20
04
03
:
:
/
/