6.17. ALARM
OPTIONS
(OPTIONAL) - ALARM VALUES
The Alarm Values menu allows the user to enter the Low or the High flow or pressure alarm value.
Alarm values will be displayed in the same Eng Units selected in Eng. Units menu. This menu is
available only if the Alarm option is purchased.
-
High Alarm Function:
The High Alarm activates if the flow or pressure exceeds the High
Alarm value and resets when the flow or pressure drops below the High Alarm value.
-
Low Alarm Function:
The Low Alarm activates if the flow or pressure drops below the Low
Alarm value and resets when the flow or pressure exceeds the Low Alarm value.
Field
Setup
Menu
Output Filter
Alarm Status
Lo Alarm Value
Alarm Options
Alarm Value
(000,000)
DP Display Format
Alarm Delay
Hi Alarm Value
Factory Defaults
(100,000)
6.18. ALARM
OPTIONS
(OPTIONAL) - ALARM DELAY
The Alarm Delay menu allows the user to enter an alarm delay of 0 to 999 seconds before an alarm will
be activated. The alarm will be reset without a delay. This display is available only if the Alarm option
is purchased.
Field
Setup
Menu
Output Filter
Alarm Status
Lo Alarm Delay
Alarm Options
Alarm Value
(000)Seconds
DP Display Format
Alarm Delay
Hi Alarm Delay
Factory Defaults
(000)Seconds
6.19. DP DISPLAY FORMAT - DISPLAYED ONLY IN PRESSURE MONITOR
MODE
The DP Display Format allows user to change number of digits shown to the right of the decimal point.
Selections are 0 to 4.
Field Setup
Menu
Output Filter
Number of Digits
Alarm Options
After Decimal
DP Display Format
Point.
Factory Defaults
(4)