6.8. AUTOZERO
(OPTIONAL) - INTERVAL
The AZ Interval menu allows the user to select the AutoZero Interval from once an hour to once a day in
1 hour increments. Use the UP/DOWN keys to select the interval value. Upon device power up, an
AutoZero cycle will occur after 20 seconds. This menu is displayed only if the AutoZero option is
purchased.
Field
Setup
Menu
Flow Correction
AZ Status
AZ Interval
AutoZero
AZ Interval
(1 TO 24HR)
Temp Comp.
AZ Test Interval
Display Filter
(1)HR
6.9. AUTOZERO
(OPTIONAL) - TEST INTERVAL
The AZ Test Interval menu allows the user to select an Auto Zero test frequency of once a minute to
once every 30 minutes in 1 minute increments. Use the UP/DOWN keys to select the interval value.
This menu is available only if the AutoZero option is purchased. If AZ Test is turned ON for more then
60 minutes, it will automatically default to OFF and the AutoZero Interval (section 5.8) will be
reactivated.
Field
Setup
Menu
Flow Correction
AZ Status
AZ Test Interval
AutoZero
AZ Interval
(ON/OFF)
Temp Comp.
AZ Test Process
Interval
Display Filter
(1)Min
6.10. TEMP. COMP. (OPTIONAL) - TEMP. UNITS
The Temperature Units menu allows the user to select the appropriate temperature units for the job. This
menu is available only if the Temp Comp. option is purchased.
Field
Setup
Menu
Flow Correction
Temp. Units
Units
AutoZero
Temp. Values
(ºF / ºC)
Temp Comp.
Temp. Input
Display Filter
Fixed value
(ºF)