OAFE-1550 Operation & Maintenance Manual
Paragon Controls Incorporated
13
Revision Level 000
6. SIGNAL PROCESSOR FIELD MENUS
To enter the Field Setup Menu; depress and hold the Enter button for 5 seconds.
6.1. OPERATING
RANGE
This menu allows the user to view the range of values possible for the user to enter as the Operating
Range. The Operating Range value entered will represent 100% process output signal (5vdc/10vdc or
20mA).
Field Setup
Menu
Operating Range
Operating Range
Zero Calibration
(ACFM)
Engineering Units
(6,000-12,000)
Lockdown
(10,000)
6.2. ZERO
PRESSURE
CALIBRATION
The Zero Calibration menu allows the user to perform a zero transducer calibration to eliminate any
transducer zero shift.
(Caution: Before performing a zero calibration, disconnect the Total (High) and Static (Low)
pressure connections, perform a zero calibration and then reconnect the Total and Static pressure
connections).
Field
Setup
Menu
Operating Range
Input Value
CPU
Taking
Zero Calibration
(0.000) in. W.C.
Samples
Engineering
Units
Lockdown
(Press Enter)
(Please
Wait)
6.3. ENGINEERING
UNITS
A list of engineering units are available for the user to select from for display purposes to meet customer
requirements. Changing the engineering units will affect the process display and the alarm value menus.
Field Setup
Menu
Operating Range
Eng. Units
Zero Calibration
Engineering Units
(ACFM)
Lockdown