7.10. 4PT FLOW CORRECTION
The 4 PT Flow Correction menu allows the user to make corrections to the display and output signal at
20% increments between 20% and 80% of Operating Range value entered. The Displayed Value is a
fixed value determined by the percentage of Operating Range. The Measured Value is the entered value
determined by an independent balancers reading.
Tech.
Config.
Password:
0000
4PT Flow Corr
80,000 CFM
Displayed
Value
Pre-Filter
60,000
CFM
80,000
MAC Address
40,000 CFM
Measured Value
Instance Number
20,000 CFM
79,500
80,000 CFM
Displayed Value
60,000 CFM
60,000
40,000
CFM
Measured Value
20,000
CFM
60,500
80,000 CFM
Displayed Value
60,000
CFM
40,000
40,000 CFM
Measured Value
20,000
CFM
40,100
80,000 CFM
Displayed Value
60,000
CFM
20,000
40,000
CFM
Measured Value
20,000 CFM
19,500
7.11. PRE-FILTER
The Pre-Filter menu allows the user to add a pre-filter to the process signal before it goes to the final
filter.
Tech. Config.
Password: 0000
4PT Flow Corr
Pre-Filter
Pre-Filter
(0-200 seconds)
MAC Address
Instance Number
(000)