21 Submenus at the server
2022/07
99E13331xx-mub-en - V08
57
Parameters
Meaning
Adjustment range
Factory setting
Cascade switchover
points
Overview for the
minimum flow rate when
a module is activated or
switched off.
-
-
Switchover point ON
Threshold for the
minimum flow rate when
the next module is
activated
70 ... 100 %
80 %
Switchover point OFF
Threshold for the
minimum flow rate when
the module switches off
0 ... 70 %
30 %
Switchover delay
Allows the activation of a
delay for
activating/switching off
00:00 ... 10:00 min
00:00 min
Duration of standby
module
Duration how long a
standby module is active
00:01 ... 07:00 hours 07:00 hours
Synchronise
Transferring the settings
from the client to the
server
Yes, No
-
21
Submenus at the server
At the server, there is only a small number of setting options available after the commissioning.
21.1
Status
Measured and balance values are measured and displayed per controller. In addition, you
receive information about the error messages, the selected service settings und the installed
firmware version. For further information, see chapter 7.
21.2
General settings
In the general settings, you can make modifications at the servers via the display. These include
luminosity, dimmed luminosity and contrast.
It is also possible to make a software update.