17 Description of function
2022/07
99E13331xx-mub-en - V08
43
Parameters
Meaning
Adjustment range Factory setting
Alarm relay
Activate the function
On, Off
Off
Relay selection
Selection of the relay
Relay 1, Relay 2
-
Inverted
Relay function inverted
On, Off
Off
Pt1000 error
Short-circuit / interruption at a
temperature sensor
On, Off
Off
VFS/US error
Short-circuit / interruption /
exceeding or falling under the
measuring range at the flow
rate sensor
On, Off
Off
μC error
μC error
On, Off
Off
Time error
Time not defined or lost
On, Off
Off
Communication error
Communication error in the
cascade network
On, Off
Off
Disinfection error
Disinfection not successfully
completed
On, Off
Off
17.7
Parallel relay
The function
parallel relay
makes it possible to switch an additional relay in case of an error.
It is possible to select what kind of incident causes the relay to be switched.
Example: The parallel relay R2 is chosen for the primary pump. Whenever the controller sends
a signal to the primary pump, the relay R2 is switched.
This can be useful to switch hydraulic paths on or off using a zone valve, for example.