40
Connect third TFT touch panel
Sequence of steps for software addressing not applicable since
address number = 1 (factory setting)
Tab. 21: Sequence of steps connection / addressing of several TFT control panels
The connection of several control panels with the same address number results in a
communication error!
The operation mode of the ventilation device is based on the last input instruction at one
of the TFT touch panels connected.
Connection of the LED control panel
3.4.4
The operation of the ventilation device is only possible with a control unit type LED control panel. For the
LED control panel in the design of the
PEHA
switch range, both on-wall and in-wall installation is
possible.
Fig 39: Adapter board with terminal X1 on an in-wall base plate; ribbon cable of the adapter board; rear
panel LED key-pad (from left to right)
The cable of the type J-Y(ST)Y 2x2x0.6 must be connected to the terminal X1 or the adapter board in
accordance with tab. Tab. 20. The ribbon cable connects the adapter board with the board of the LED
key-pad.
Do not pull the ribbon cable off the adapter board, but put the LED control panel
diagonally through the PEHA frame!
Connection of external boost ventilation switch
3.4.5
The boost ventilation mode can be activated by actuating one or more boost ventilation switches
connected in parallel. The switches which are usually installed in the design of the respectively used
switch range are triggered when the boost ventilation mode is activated. The potential-free connection
between the sensor and the through terminal X10 is established by means of a cable with at least 2 wires
(recommendation: cable type J-Y(ST)Y 2x2x0.6). The introduction of the cable in the NOVUS is realised
in one of the pre-cut cable bushings.
Through terminal X10
Wire cable boost ventilation switch
X10.4 Wire
1
X10.5 Wire
2
(GND)
Tab. 22: Terminal assignment connection boost ventilation switch
Connection of external sensors
3.4.6
The operating mode
Automatic sensor
auf the automatic mode is controlled by an analogue sensor
signal which is generated by one or more sensors. The connection between the sensor module and the
X1
Summary of Contents for NOVUS 300
Page 1: ...Version 2 0_10 2014 EN...
Page 59: ...59 Dimensional sketch 3 9 5 Fig 47 Dimension drawing HRU NOVUS...
Page 60: ...60 Plant 1 circuit diagram NOVUS 3 9 6...
Page 61: ...61 Plant 2 circuit diagram NOVUS with integrated defroster 3 9 7...
Page 62: ...62 Plant 3 Terminal scheme of through terminal X10 3 9 8...