Symbol Designation
Explanation / actions
Button
Fan speed 1 (FS1)
Using the button Fan speed 1, activate FS1 and parameterise
it with the navigation buttons.
Setting range: 17 % < FS1 < FS2
Button
Fan speed 3 (FS3)
Using the button Fan speed 3, activate FS3 and parameterise
it with the navigation buttons.
Setting range: FS2 < FS3 < 100 %
Duration boost ventilation
Settings: 15 min …120 min,
whereby the air volume flow of the boost ventilation
corresponds to fan speed 3.
Ventilation intensity for
the duration of non-
occupation for humidity
protection
Settings: 15 min/h, 30 min/h, 45 min/h,
whereby the ventilation intensity of the active duration of the
time interval corresponds to fan speed 1.
Tab. 5: Parameterisation submenu fan speeds
2.3.2.2 Submenu
Filter
The following can be set / read here:
•
Filter run-time in 10-day-steps
•
Current remaining run-time of the filter
•
Retting of the filter run-time and the counter for exceeding the filter run-time
Symbol
Designation
Explanation / actions
Duration of the filter run-
time
Setting: 30 d … 180 d, using the navigation buttons
whereby a maximum filter run-time of 90 days is
recommended.
Remaining run-time of the
filter
Display of the current remaining run-time of the filter
Display field
Reset filter run-time
Using the button Checkmark and Enter, the filter run-time can
be reset to the pre-set value.
Tab. 6: Parameterisation submenu filter
2.3.2.3 Submenu Frost protection
Here, the frost protection mode can be set using the navigation buttons:
•
Eco
•
Safe
•
Moisture heat exchanger (enthalpy exchanger) with own anti-freeze protection threshold
Symbol
Designation
Explanation / actions
Display field
Frost protection mode
Eco
In this “eco mode” however, there is a residual risk of freezing
of the heat exchanger. The energy required for frost protection
is lower.
Display field
Frost protection mode
Safe
In the “safe” mode, freezing of the heat exchanger is
absolutely prevented. The energy required for frost protection
is higher.
Display field
Frost protection mode
Moisture heat exchanger
In the mode Moisture heat exchanger, freezing of an enthalpy
exchanger (membrane moisture heat exchanger) is basically
prevented.
Tab. 7: Parameterisation submenu frost protection
Summary of Contents for NOVUS 300
Page 1: ...Version 2 0_10 2014 EN...
Page 59: ...59 Dimensional sketch 3 9 5 Fig 47 Dimension drawing HRU NOVUS...
Page 60: ...60 Plant 1 circuit diagram NOVUS 3 9 6...
Page 61: ...61 Plant 2 circuit diagram NOVUS with integrated defroster 3 9 7...
Page 62: ...62 Plant 3 Terminal scheme of through terminal X10 3 9 8...