Fan speed (FS) Time slot (time 0
00
- 24
00
)
FS1
8
30
- 16
00
FLS2
0
00
- 8
00
16
00
- 24
00
FLS3
8
00
– 8
30
Tab. 9: Time slot factory setting, group weekdays Mo-Fr
Fig 10: Automatic timing factory setting, group weekdays Sat-Sun
Fan speed (FS) Time slot (time 0
00
- 24
00
)
FS2
0
00
- 24
00
Tab. 10: Time slot factory setting, group weekdays San-Sun
The factory setting of the automatic timing can only be reactivated via the main menu
Setup.
If the operating mode “Automatic timing” is active in automatic mode, the active fan speed (FS 1-3 only)
is, in accordance with the time slot, visualised in grey on the start menu in addition to the icon Automatic
mode.
Fig 11: Automatic mode automatic timing with active fan speed FS2
2.3.2.4.2 Automatic
sensor
The operating mode
Automatic sensor
of the automatic mode requires the connection of an external air
quality / CO
2
or humidity sensor to the control of the ventilation device. The analogue signal of the sensor
is taken as control signal for the fan rotary speed of the ventilation device. When applying several sensors
in one ventilation plant, the output signal of a maximum value module is used for the control of the
ventilation device.
At first, using the navigation buttons (red background of the text) and by setting the checkmark, it is
selected whether the sensor has a current output or voltage output (current: 4…20 mA, voltage: 0…10 V),
and this is confirmed with Enter. Subsequently, the lower point (range start parameter p1) and the upper
Summary of Contents for NOVUS 300
Page 1: ...Version 2 0_10 2014 EN...
Page 59: ...59 Dimensional sketch 3 9 5 Fig 47 Dimension drawing HRU NOVUS...
Page 60: ...60 Plant 1 circuit diagram NOVUS 3 9 6...
Page 61: ...61 Plant 2 circuit diagram NOVUS with integrated defroster 3 9 7...
Page 62: ...62 Plant 3 Terminal scheme of through terminal X10 3 9 8...