If connecting leads and electric animal fence wires are installed
near an overhead power line, the clearances shall not be less
than those shown in the table.
Minimum clearances from power lines for electric animal fences
Power line voltage
Clearance
≤1000 V
3 m (10')
>1000 V to ≤33,000 V
4 m (13')
>33,000 V
8 m (27')
If connecting leads and electric animal fence wires are installed
near an overhead power line, their height above the ground shall
not exceed 3 m (10'). This height applies to either side of the
orthogonal projection of the outermost conductors of the power
line on the ground surface, for a distance of:
2 m (6'6") for power lines operating at a nominal voltage not
exceeding 1000 V.
15 m (50') for power lines operating at a nominal voltage
exceeding 1000 V.
To prevent lightning damages you have to install lightning pro-
tection (spark gap with earthing) in the leadout cable before you
run it inside a building which is not liable to catch fire.
Electric animal fences intended for deterring birds, household pet
containment or training animals such as cows need only be sup-
plied from low output energizers to obtain satisfactory and safe
performance.