38
PAW3500-VES
PAW3500-VES Compact systems
System manual
IT
8.7.4 SENDING OUT OF A LIVE EMERGENCY NOTICE FROM REMOTE STATIONS
1)
Lift the safety lid on the station and press the
EMERGENCY
key once. It lights up steadily.
The fact that the system has been placed in a state of emergency by the station is shown also on any other stations.
2)
Select the zones where the message should be sent.
3)
Activate the EVAC message or the ALERT message by means of the appropriate button or speak through the microphone
keeping the PTT key pressed until the end of the message.
Note: The PTT key has priority over any pre-recorded messages being sent out.
4)
If necessary, repeat the sequence of points
2)
and
3)
above several times.
5)
To end the state of emergency, press
EMERGENCY
button again.
8.7.5 EXIT OF THE SYSTEM FROM MANUAL MANAGEMENT OF AN EMERGENCY
At the end of the procedure for managing a Manual Emergency, press the red EMERGENCY key, which will extinguish and – if
there is no activation taking place from external peripheral units connected to the controlled input contacts – the system will return
automatically to its Idle state, displaying the MUSIC MENU.
The ALARM LED will extinguish to indicate that the VOICE ALARM has been deactivated.
If, on the other hand, any of controlled inputs have been activated, the EMERGENCY button will start to
fl
ash and the system will
remain in a state of Automatic Emergency, resuming the broadcasting of the messages in the various areas, depending on how
the activated inputs were programmed.