5
System manual
PAW3500-VES Compact systems
IT
PAW3500-VES
2. INTRODUCTION
2.1 OVERVIEW OF THE SYSTEM
The
PAW3500-VES
range includes “light” voice evacuation systems for emergency facilities, designed speci
fi
cally for wall-
mounting and equipped with control units, certi
fi
ed in compliance with
EN 54-16:2008 / EN 54-4
standards. The
PAW3502-V
model is capable of managing
2
zones
, each driven by a single ampli
fi
er, as well as remote microphone stations and controlled
inputs to be connected to a central
fi
re-
fi
ghting system.
2.2 FUNCTIONAL FEATURES
•
Rated audio output: 500 W overall, distributable freely among the 2 zones with a maximum limit of 250 W per single zone.
•
Backlit 4.3” display with touch screen for selecting the alert and evacuation zones and enabling navigation for adjusting
volume levels, con
fi
guring the equipment and viewing failures.
•
Handheld
fi
reman’s paging microphone.
•
Sending out of pre-recorded EVACUATION and ALERT messages.
•
7 off controlled input contacts, con
fi
gurable for playing the evacuation and/or alert messages to the programmed zones or
for resetting the messages.
•
One off music input for sound sources.
•
One
off con
fi
gurable relay outputs.
•
Double A+B output for each zone.
•
Protected local button for placing the system in an emergency state, equipped with its own LED.
•
Local button for resetting the fault acoustic signal and stopping playing out of alarm messages.
•
EN54-4 certi
fi
ed internal battery charger unit for 24Vdc secondary power supply.
•
Up to 4
PMB132
remote emergency units can be connected.
Summary of Contents for PAW3500-VES