PAW3500-VES
PAW3500-VES Compact systems
System manual
IT
set> IMP. REFERENCE
Impedance acquisition and tolerance setting
Panel for acquiring line impedance values and setting the tolerance threshold for
the diagnostic tests.
Press the appropriate buttons to access the sub-panels.
The
Zone impedance reference
panel shows the impedance values measured
on the output zones, which will constitute the reference values.
Use the
set>Impedance tolerance set
panel to de
fi
ne the tolerance, choosing
one of the suggested values (press the
Change
key associated with the desired
zone and set one of the following values: 10%, 20%, 30%, 40% or 50%).
When the diagnostic system detects a value beyond the tolerance chosen for
the reference value, a ‘Fault’ is activated.
To return to the CONFIGURATION menu, press
Escape
.
set> 20KHZ LEVELS
Setting the test signal level
Panel for setting the test signal levels to 20 kHz in the various audio channels.
Press the Change keys associated with the level to be adjusted and select one
of the following options:
level 1
,
level 2
,
level 3
or
Off
. The recommended value
for the ampli
fi
ers is
2
.
To return to the CONFIGURATION menu, press
Escape
.
set> ALARM LEVELS
Setting the alarm source level
Panel for setting the output volume of the alarm sources connected
to the
PAW
.
- Emergency units.
- Hand-held paging local microphone.
- Evacuation message.
- Alert message.
To return to the CONFIGURATION menu, press
Escape
.