65
2K-Tower
199*466*337mm
35.5kg
3K-Tower
199*466*337mm
39.1 kg
Table 14. Electrical Input (All Models)
Nominal Frequency
50/60 Hz auto-sensing
Frequency Range
45–55 Hz(50Hz)/55-65Hz(60Hz) before transfer to
battery
Bypass Voltage
Range
+5%,+10%,+15%,+25% (+25% by default),
-20%,-30%,-45% (-45% by default)
Table 15. Electrical Input (All Models)
Model Default Input
(Voltage/Current)
Selectable Input
Voltages
Voltage Range at
100% Load
1K
230V /
4.4A
200, 208, 220, 230,
240
200*-290 Vac
2K
230V /
8.7A
200, 208, 220, 230,
240
200*-290 Vac
3K
230V /
13.0A
200, 208, 220, 230,
240
200*-290 Vac
* If rated input voltage selected is 200V, the low limit is 180V. If rated input
voltage selected is 208V, the low limit is 190V. Under other condition the low
limit is 200V. The above-mentioned voltage is the input voltage window for
the UPS with PF0.9. On the contrary, the input voltage window can be varied
from 110Vac to 290Vac depending on the load percentage of connected
equipment.
Table 16. Electrical Input Connections (All Models)
Model Input Connection
Input Cable
1K
IEC320 C13-10A
IEC320 C14-10A
2K
IEC320 C20-16A
IEC320 C19-16A