4.5.5 DATA LOGGER SETUP MODE CONFIGURATION PROCEDURE
The Data logger setup mode allows the entry, review, or altering of the datalog settings.
4.5.5.1 ENTERING THE DATA LOGGER SETUP MODE
From the Operation or any other mode code, depress the SCROLL key until
dLS
is displayed.
With
dLS
in the top display, depress the DOWN key to enter the mode. If
dLS
does not
appear, then the mode has been disabled. Refer to Table 4-1 (page 25) for Enable mode
instructions.
4.5.5.2 MOVEMENT IN THE DATA LOGGER SETUP MODE
Each time the DOWN key is depressed while a parameter code is being displayed, another
parameter code will be displayed.
Depressing the SCROLL key while a parameter code is displayed will cause the parameter
value to appear. Depressing the SCROLL key with a parameter value displayed will cause
the next parameter code to come up in the display.
Depressing the UP key while a parameter code is being displayed will exit the Data logger
Setup mode and
dLS
will appear in the display. Using the SCROLL key at this point will
allow you to proceed to any other mode.
4.5.5.3 DATA LOGGER SETUP MODE CONFIGURATION
Refer to Table 4-4 (page 30) for configuration procedures for the Datalog Setup mode.
4.5.6 PRESET ADJUST MODE CONFIGURATION PROCEDURE
(TOTALIZATION OPTION ONLY)
The Preset mode allows the entry, review, and altering of the preset parameters. These
parameters are used to trigger relays at selected totalization totals.
4.5.6.1 ENTERING THE PRESET ADJUST MODE
From the Operate or any other mode code, depress the SCROLL key until
PSA
is displayed.
This is the mode code for the Preset Adjust mode. With
PSA
in the top display, depress the
DOWN key to enter the mode. If the
PSA
code does not appear, then the mode has been
disabled. Refer to Table 4-1 (page 25) for Enable mode instructions.
4.5.6.2 MOVEMENT IN THE PRESET ADJUST MODE
The preset values will be changeable in the Preset Adjust mode as follows: With the
PSA
mode code displayed, depress the DOWN key.
PS1H
(preset high value) will be displayed in
the upper display, assuming that the Preset has been selected in the Program mode. When
the SCROLL key is depressed, the value will be displayed. The UP or DOWN keys can now
be used to increment or decrement the value by a factor of ten thousand (10,000) units per
depression. When the SCROLL key is depressed again,
PS1L
(preset low value) will be
displayed. The UP or DOWN keys can now be used to increment or decrement the values by
single units (ignoring the decimal position). When the SCROLL key is depressed again, the
next preset code will be displayed in the appropriate display. Refer to Table 4-5 (page 31).
4.5.6.3 PRESET ADJUST MODE CONFIGURATION
Refer to Table 4-5 (page 31) for configuration procedures for the Preset Adjust mode. All
possible paramters are shown for illustration purposes. Only those parameters applicable to
each respective pen will actually be shown. Access to either Pen 1 or Pen 2 parameters may
be quickly obtained by depressing the DOWN key at either the
PEn1
or
PEn2
code.