Parker V200 Product Bulletin Download Page 13

Page 14 / Bulletin 75-00 J

Symptom

Possible Cause

Solution

Strong Ammonia 
smell coming 
from bubbler 
(#14).

Water make up closed or restricted.

Leaking vent solenoid (#6).

Make sure the fresh water supply to the bubbler is not turned 
off or being restricted. The purger is supplied with a shutoff ball 
valve that should be in the full open position to start, and then 
throttled back to control the fl ow rate into the bubbler.

Check the operation of the water makeup solenoid (#5). Verify 
that the coil is energized when the vent cycle is active. The 
magnetic fi eld can be verifi ed with a small screwdriver touching 
the top of the solenoid tube. It should be drawn to the tube if the 
coil is powered and functioning properly. If the coil functions and 
water still does not fl ow to the bubbler, check the supply lines for 
obstructions. 

Replace the water solenoid (#5) if necessary.

If bubbles are seen in the bubbler well after a vent has occurred, 
the vent solenoid may be leaking. 

Replace the solenoid if necessary.

Slave unit (#2)
not functioning (5 
purge points and 
up).

Master, slave communication cable 
missing or damaged.

No power supplied to slave board.

Verify that the communications cable connecting the main purger 
controller to the slave board is present, attached to the proper 
terminals and is not damaged.

Check to make sure the green LED at the top of the slave unit 
(#2) circuit board is fl ashing. 

Verify the proper communication setting. This is done by pressing 
the up & down arrow keys on the main controller (#1) at the same 
time.  Several attempts may be required as timing is critical. After 
successfully completing this step, you should see a menu screen 
that displays; Baud Rate, Parity, Temperature Scale and Slave ID.                                                                            
(See step #7 under installation instructions)

Make sure the “baud” rate is set for 19200, “parity” even and 
“slave ID” 01. Use the same keypad strokes to move and enter 
settings as described in the bulletin under “Setup Instructions”. 
Press the menu key to get back to the main screen. Check the 
operation of the slave unit.  

Make sure the power cable from the main purger controller to the 
slave board is present, not damaged and properly connected.
Replace slave unit if necessary. (See both 4 point purger and 
slave unit wiring diagram for proper wiring terminals)

Controller in 
“sleep mode”, will 
not purger

No foul gas present in system.

Damaged main controller board.

The purger controller will automatically go into “Sleep Mode” if 
it has sampled every programmed purge point twice without a 
vent occurring. It will stay in sleep mode for 2 hours then resume 
its programmed cycle. You can override the sleep mode cycle 
by simply pressing the “Enter” key on the controller. The sleep 
mode feature will not be disabled and will repeat again if no vent 
occurs. 

Replace controller if necessary.

Note:

  all items with a (#) can be located in the V200 auto purger parts diagram.

V200 Service Pointers Continued

Summary of Contents for V200

Page 1: ...ration systems Product Features Smaller compact design with equivalent capacity of our current model Light weight 29 5 kg 65 lbs Proprietary microprocessor control for all sensing and control function...

Page 2: ...nsing pressure runtime of the compressors and operating costs Non condensable indicators are excessively high condensing temperatures pressures and saturated temperature pressure deviations One indica...

Page 3: ...e without a vent occurring the system will shut off for two hours Purge Cycle The purge cycle consist of three main operations fill pre cool separating non condensable gases refrigerant and the releas...

Page 4: ...require lower temperatures to condense Condensed refrigerant and non condensable gases rise through the heat exchanger and into the vapor vent As the liquid rises it lifts an orifice flow controller t...

Page 5: ...the float will fall allowing the non condensable gases to escape through the orifice Non condensable gases will continue to accumulate producing an elevated pressure Once the pressure of the non conde...

Page 6: ...ee electrical wiring diagram Contractors need to follow a WPS Welding 3 Procedure Specification for all welding The procedure must be qualified and welder doing the weld qualified to perform that proc...

Page 7: ...s the Enter key to return to the main menu 2 When in the main operating screen press and release the Menu button Use the up down arrow buttons to select the Setup option Press and release the Enter bu...

Page 8: ...e the up down arrow key to highlight the Time Based option Press and release the Enter key to save your selection The next step is to enter the time the purge cycle will start Use the up Down arrow ke...

Page 9: ...Bulletin 75 00 J Page 9 V200 Auto Purger Electrical Wiring Diagram for a 4 Point Purger V200 Auto Purger Compact Design Dimensions 1 2 3 16 4 9 7 8 6 11 10 5 12 13 14 15 17 18 19 20 21 12 10 3 10...

Page 10: ...Nylon 208669 Conversion Kit Steel Tube Cabinet Style to Nylon 208670 15 Liquid Drainer 1 2 Threaded Connection 309625 16 Gage 30 150 psig R717 309401 Gage 760mm 10 5 bar R717 309403 17 Optical Level...

Page 11: ...shown on the purge point solenoids connections are common to the relay Incoming line power 120 240 volts should be supplied to these terminals An incoming natural should be supplied to one of each of...

Page 12: ...This is located on the upper left side of the front panel 1 Check optical level sensor 17 for proper operation Loose wire defective sensor Replace if necessary Check liquid supply orifice 11 for obst...

Page 13: ...he slave unit 2 circuit board is flashing Verify the proper communication setting This is done by pressing the up down arrow keys on the main controller 1 at the same time Several attempts may be requ...

Page 14: ...and tube clamp from kit along with check valve assembly as shown in the cutaway view Tubing ends may need to be trimmed back for proper fit 3 Remove and discard steel lines fittings and bubbler 4 Rein...

Page 15: ...ory This warranty is in force only when products are properly installed field assembled maintained and operated in use and service as specifically stated in Refrigerating Specialties Catalogs or Bulle...

Reviews: