isysNet 32 Point Valve Driver, Series A (PSSV32A) 

E100P

8

32 Point Valve Driver

Outputs per Module 

32, sourcing

Voltage Drop, On-State Output, Maximum 

0.2VDC

Voltage, Off-State Output, Maximum 

28.8VDC 

Voltage, On-State Output, 
  Maximum 

28.8VDC 

  Minimum 

10VDC 

  Nominal 

24VDC

Output Current Rating 

200 mA per channel, not to exceed 6.0 A per module

Output Surge Current, Maximum 

0.5 A for 10 ms, repeatable every 3 seconds

Current Leakage, Off-State Output, Maximum 

0.1 mA

Current, On-State Output Minimum 

200 mA per channel

Output Delay Time OFF to ON, Maximum

1

 

0.1 ms

Output Delay Time, ON to OFF, Maximum

1

 

0.1 ms

External DC Power Supply Voltage Range 

10 to 28.8VDC

External DC Power Supply Voltage Nominal 

24VDC

General Specifications

LED Indicators 

1 output status 

 

1 green/red network status, logic side 

 

1 green/red module status, logic side

PointBus Current, Maximum 

75 mA @ 5VDC

Operating Temperature 

IEC 60068-2-1 (Test Ad, Operating Cold), 

 

IEC 60068-2-2 (Test Bd, Operating Dry Heat), 

 

IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 

 

-20 to 60°C (-4 to 140°F)

Storage Temperature 

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold), 

 

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat), 

 

-40 to 85°C (-40 to 185°F)

Relative Humidity 

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 

 

5 to 95% non-condensing

Shock 

IEC60068-2-27 (Test Ea, Unpackaged Shock): 

 

Operating 30g 

 

Non-operating 50g

Vibration 

IEC60068-2-6 (Test Fc, Operating): 

 

5g @ 10 to 500Hz

ESD Immunity 

IEC 61000-4-2: 

 

6kV contact discharges 

 

8kV air discharges

Radiated RF Immunity 

IEC 61000-4-3: 

 

10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz 

 

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz 

 

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity 

IEC 61000-4-4: 

 

±3kV at 5kHz on signal ports

Surge Transient Immunity 

IEC 61000-4-5: 

 

±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity 

IEC 61000-4-6: 

 

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions 

CSPR 11: 

 

Group 1, Class A

Enclosure Type Rating 

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque 

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Wiring Category

2

 

1 - on signal ports

Certifications: 

c-UL-us  UL Listed Industrial Control Equipment, 

(when product is marked) 

 

certified for US and Canada

 

CE

 

European Union 89/336/EEC EMC Directive, 

 

 

compliant with: 

 

 

EN 61000-6-4; Industrial Emissions 

 

 

EN 50082-2; Industrial Immunity 

 

 

EN 61326; Meas./Control/Lab., Industrial Requirements 

 

 

EN 61000-6-2; Industrial Immunity

 

C- Tick  Australian Radiocommunications Act, compliant with: 

 

 

AS/NZS CISPR 11; Industrial Emissions

1.  OFF to ON or ON to OFF delay is time from a valid output “on” or “off” signal to output energization or de-energization.
2.  Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.

Specifications

 – 

Following are specifications for the 32 point valve driver.

Summary of Contents for PSSV32A

Page 1: ...ubject to change by Parker Hannifin Corporation and its subsidiaries at any time without notice EXTRA COPIES OFTHESE INSTRUCTIONS ARE AVAILABLE FOR INCLUSION IN EQUIPMENT MAINTENANCE MANUALSTHAT UTILI...

Page 2: ...s Attentions help you Identify a Hazard Avoid a Hazard Recognize the Consequence SHOCK HAZARD Labels may be located on or inside the equipment to alert people that dangerous voltage may be present BUR...

Page 3: ...ase or communication adapter Wire the 32 Point Valve Driver Following are wiring instructions for the 32 point valve driver Use the appropriate harness assembly based on your manifold wiring interconn...

Page 4: ...Tools EDS Hardware Installation Tool to load the EDS file to RSLinx Step 2 Configure the DeviceNet Scanner Subnet Reference Chapter 4 of the isysNet DeviceNet Adapters User Manual PSS UM001 for detai...

Page 5: ...oint Valve Driver EDS file to RSLinx Download EDS file from www parker com pneu isysNet On your computer follow Start Rockwell Software RSLinx Tools EDS Hardware Installation Tool to load the EDS file...

Page 6: ...Driver in Profibus Step 1 Configure Valve Driver Module in SST Profibus Configuration Utility Note SST PFB CLX is used here for example For different Profibus scanners refer to appropriate documentati...

Page 7: ...eted dup_MAC id test Device not powered check module status indicator Flashing Green Device is on line but has no connections in the established state Green Device is on line and has connections in th...

Page 8: ...rating 30g Non operating 50g Vibration IEC60068 2 6 Test Fc Operating 5g 10 to 500Hz ESD Immunity IEC 61000 4 2 6kV contact discharges 8kV air discharges Radiated RF Immunity IEC 61000 4 3 10V m with...