If your RSLogic 5000 is Version 13.X:
• Highlight the
1738-AENT
under I/O configuration, right click and
select
New Module
.
• Choose the
Generic 1738
module from the list of Allen-Bradley
modules.
• Enter a name (optional), an appropriate slot number and the
connection parameters as shown in this screen capture.
• Choose
Next
to set
RPI.
• Choose
Finish
. Notice that the 32 Point Valve Driver Module is
now under the I/O configuration.
Step 5: Access Module Data via the PSSCENA or 1738-AENT
Adapter and Create Ladder Program.
• Make sure the 32 outputs of PSSV32A appear in Controller Tags.
Use the information in the ladder logic program to access module
data.
• Reference pages 4-13 through 4-14 of Rockwell publication 1734-
UM011 for similar information.
Step 6: Download the Program to the Controller
• Reference pages 4-13 through 4-14 of Rockwell publication 1734-
UM011 for similar information.
isysNet 32 Point Valve Driver, Series A (PSSV32A)
E100P
6
Setup the 32 Point Valve Driver in Profibus
Step 1: Configure Valve Driver Module in SST Profibus
Configuration Utility
Note: SST-PFB-CLX is used here for example. For different
Profibus scanners, refer to appropriate documentation for setup
information.
• Download GSD file from www.parker.com/pneu/isysNet
• In SST Profibus Configuration Utility, follow
Library
➔
Add GSD
to load the GSD file to SST Profibus.
• In SST Profibus Configuration Utility, follow
Browse
➔
Search for
devices
to load the GSD file to SST Profibus
• Right click on the found device, follow
GSD files
and click on
appropriate GSD for PSSV32A.
• Add PSSV32A as slave to SST-PFB-CLX master.
• Detailed information can be found in the SST-PFB-CLX User Guide
(Ver. 1.4 715-0022), which is available on www.woodhead.com.
Step 2: Add SST Profibus Scanner in RSLogix 5000
I/O Configuration
• Add SST-PFB-CLX scanner I/O configuration. Reference pages 36
to 39 of the SST-PFB-CLX User Guide, for detailed information.
• Notice that the SST-PFB-CLX scanner is now under the I/O
configuration.
Step 3: Access Module Data via the SST-PFB-CLX Scanner
and Create Ladder Program.
• Reference Chapter 7 of the SST-PFB-CLX User Guide for
addressing information.