![Parker PSSV32A Installation & Service Instructions Manual Download Page 7](http://html1.mh-extra.com/html/parker/pssv32a/pssv32a_installation-and-service-instructions-manual_3792681007.webp)
isysNet 32 Point Valve Driver, Series A (PSSV32A)
E100P
7
Troubleshoot With the Indicators
Mod
PSSV32A
Net
Fault
PSSV32A
Module Status
Indicator
Network Status
Indicator
Output Fault Status
Indicator
Indication
Probable Cause
Module Status
Off
No power applied to device
Green
Device operating normally
Flashing Green
Device needs commissioning due to
missing, incomplete, or incorrect
configuration
Flashing Red
Recoverable fault
Red
Unrecoverable fault -
may require device replacement
Flashing Red/Green Device is in self-test
Indication
Probable Cause
Network Status
Off
Device is not on line:
- Device has not completed
dup_MAC-id test.
- Device not powered - check module
status indicator.
Flashing Green
Device is on line but has no
connections in the established state.
Green
Device is on line and has
connections in the established state.
Flashing Red
One or more I/O connections in
timed-out state.
Red
Critical link failure - failed
communication device. Device
detected error that prevents it from
communicating on the network.
Flashing Red/Green Communication faulted device - the
device has detected a network access
error and is in communication faulted
state. Device has received and accepted
an Identity Communication Faulted
Request - long protocol message.
Indication
Probable Cause
Output Fault Status
Off
Outputs operating normally
Red
Over current, short circuit or over
temperature detected on one or more
outputs. (On-State only)