- 22 -
PARAMETER SETUP
Follow the procedure below to set the parameters such as flow rate deviation alarm, upper and lower limit
flow rate and event output delay time:
1. After introducing power to the MFC, press the [
DISP
] key twice (2X) to display the totalized flow
rate (‘
L
’ lamp lights).
2. Press the [
<
] key for three (3) seconds (the upper display indicates
‘
0.r
∩
9
’
[parameter setup
mode]).
3. Press either the [
∧
∧
∧
∧
] or [
∨
∨
∨
∨
] key until the desired setup item number is indicated.
4. Press the [
ENT
] key (the present setting value indicated on the lower display blinks).
5. Press either the [
∧
∧
∧
∧
] or [
∨
∨
∨
∨
] key to select the desired setting value (move to the digit to be changed
by pressing the [
<
] key). Press the [
ENT
] key to store the selected value. If the [
DISP
] key is
pressed prior to pressing the [
ENT
] key, the setting value remains at the previous value without
being updated.
6. Repeat steps 3, 4 and 5 for any setup item requiring programming. Once setup items are
completed, proceed to step 7.
7. Press the [
DISP
] key to return to the instantaneous flow rate display, the display shown after
introducing power.
Note: If no operation is performed for one (1) minute after entering the parameter setup mode, the
display automatically returns to the instantaneous flow rate display.
PARAMETER SETUP ITEM LIST
Reference
No.
Display
Parameter Description
Factory
Setting
Setting Range
Refer to
Function Setup
Item
Remarks
1
0.r
∩
9
*
1
Flow rate OK judgment
range
(2% FS)
*
10
(0.5 to 100% FS)
*
10
2
0.HYS
*
1
Flow rate OK judgment
hysteresis
(1% FS)
*
10
(0.5 to 100% FS)
*
10
C-07
,
C-08
3
A. HI
*
2,
*
3
Flow rate deviation upper
limit alarm
(10% FS)
*
10
(0.5 to 100% FS)
*
10
4
A.H.HY
*
2,
*
3
Flow rate deviation upper
limit alarm hysteresis
(2% FS)
*
10
(0.5 to 100% FS)
*
10
5
A. Lo
*
2,
*
3
Flow rate deviation lower
limit alarm
(10% FS)
*
10
(0.5 to 100% FS)
*
10
6
A.L.HY
*
2,
*
3
Flow rate deviation lower
limit alarm hysteresis
(2% FS)
*
10
(0.5 to 100% FS)
*
10
Unit: SLPM
7
A.dLY
*
3
Flow rate deviation alarm
judgment delay time
10.0 seconds
1.0 to 999.9
seconds
C-07
,
C-08
,
C-15
,
C-16
8
E.l,dL
*
4
Event output 1 delay time
9
E.2.dL
*
4
Event output 2 delay time
0.0 seconds
0.0 to 999.9
seconds
C-07
,
C-08
Even if the delay time is
set, it is disabled during
selection of totalization
pulse output.
10
C,F,
*
5
User setup conversion
factor
1.000
0.100 to 9.999
C-18
11
E.1.SP
*
6
Event output 1 upper/lower
limit flow rate setup
12
E.2.SP
Event output 2 upper/lower
limit flow rate setup
(0% FS)
*
10
(0 to 100% FS)
*
10
C-07
,
C-08
Unit: SLPM
13
A.SCL
*
7
Analog optional scaling
(100% FS)
*
10
(10 to 100% FS)
*
10
C-28
The maximum flow rate
is set.
Unit: SLPM
14
E.A.Lo
*
8
Totalized event flow rate
(lower 4 digits)
15
E.A.HI
*
8
Totalized event flow rate
(upper 4 digits)
0
0 to 9999
C-07
,
C-08
,
C-13
16
P.0.dL
*
9
PV
forced zero function
3.0 seconds
0.0 to 999.9
seconds
C-29