Page 9 /15
P2M2HBVT12400
User Manual
30060921401W05
February 2018
Pneumatic Division
27031 Evreux - France
Power supply diagnostic through LED
The P2M Node 24DO monitors the auxiliary power supply voltage and manages two levels of diagnostics;
warning and error range. The normal range can be modified through Manufacturing Specific Objects.
Auxiliary Power Management
Auxiliary Power Supply
LED function details:
•
‘’Auxiliary power’’ error is active from 9 to 18
Vdc or above 28,5 Vdc
•
When ‘’Auxiliary power error’’ is active, LED is solid red
Green LED
LED
Status
Description
Solving
OFF
Auxiliary lines not
powered
Check Auxiliary power
supply
ON
GREEN
Standard mode
(Auxiliary power within
normal range 20,0V*
to 26.4V*)
N/A
Blinking
Green
Auxiliary power in
Warning range
Check Auxiliary power
supply
Check/reset adjusted
values
ON
RED
Auxiliary power in
Error range. Module in
Failsafe status
Check and restore
Auxiliary power supply,
then acknowledge the
error
* Warning level values could have been modified
by the user!
1s
50% 50%
Power supply diagnostic through Network and Process Data mapping
Index
Data Type
Access
Name
Min Value
Max Value
Default
0x200B
UINT
Read / Write
AUX Voltage Warning Low Limit
18000
24000
20000
0x200C
UINT
Read / Write
AUX Voltage Warning High Limit
24000
28500
26400
Auxiliary power supply range adjustment
Normal auxiliary power supply voltage range is set by default as 20,0V < Aux power supply < 26,4V
The low and high limits of the Voltage Warning levels are adjustable via the Manufacturing Specific Object
“
AUX Voltage Warning Low
Limit”
and
“AUX
Voltage Warning High
Limit”
Values shown in mV.
•
Diag 1 : Auxiliary Voltage in Warning range. The limits of the Warning range can be adjusted via the Objects
“
AUX
Voltage Warning Low
Limit”
and AUX Voltage Warning High
Limit”
•
Diag 2 : Auxiliary Voltage failure. If AUX Voltage < 18 Vdc or > 28,5 Vdc. Module goes into Failsafe Status.
Acknowledge is required to restart the module. Values cannot be adjusted.
Byte 0
Diag
7 ………………......
Diag 0
0
7
PLC mapping Process input
6
5
4
3
2 1
Index Data Type
Access
Name
Min Value
Max Value
Default
0x2004
UINT
Read
AUX Voltage
0
36300
N/A
Auxiliary Voltage Reading
The auxiliary voltage measured by the module can be accessed via the Object
“AUX Voltage”
. The displayed
value is in mV.