Page 11 /15
P2M2HBVT12400
User Manual
30060921401W05
February 2018
Pneumatic Division
27031 Evreux - France
Manufacturer Specific Objects
The manufacturer object are:
Index
Subindex
Type
Access
Name
0x2001
0x00
USINT
RO
Number of entries (0x03)
0x2001
0x01
USINT
RW
Solenoids (Channel 1 to 8) **
0x2001
0x02
USINT
RW
Solenoids (Channel 9 to 16) **
0x2001
0x03
USINT
RW
Solenoids (Channel 17 to 24) **
0x2002
0x00
USINT
RO
Number of Entries (0x18)
0x2002
0x01
UDINT
RO
Switching Cycles (Channel 1)
…
…
…
…
…
0x2002
0x18
UDINT
RO
Switching Cycles (Channel 24)
0x2003
0x00
USINT
RO
Number of Entries (0x03)
0x2003
0x01
USINT
RW
Clear Switching Cycle (Channel 1 to 8)
0x2003
0x02
USINT
RW
Clear Switching Cycle (Channel 9 to 16)
0x2003
0x03
USINT
RW
Clear Switching Cycle (Channel 17 to 24)
0x2004
0x00
UINT
RO
AUX Voltage Reading
0x2005
0x00
UINT
RO
Module Error
0x2006
0x00
USINT
RO
Number of Entries (0x03)
0x2006
0x01
USINT
RO
Channel Error (Channel 1 to 8) **
0x2006
0x02
USINT
RO
Channel Error (Channel 9 to 16) **
0x2006
0x03
USINT
RO
Channel Error (Channel 17 to 24) **
0x2007
0x00
UINT
RO
Module Info Flags **
0x2008
0x00
USINT
RW
System Commands **
0x2009
0x00
UINT
RO
Module Error Input **
0x200B
0x00
UINT
RW
AUX Voltage Warning Limit Low
0x200C
0x00
UINT
RW
AUX Voltage Warning Limit High
0x200D
0x00
UINT
RW
Output State Behavior
Index
Data
Type
Subindex
Access
Name
Min Value
Max Value
Default
0x2001
USINT
0x01 to 0x03
Read / Write
Solenoids
0
0xFF 0xFF 0xFF
0
Process Data Outputs
Manufacturer Specific Object
“Solenoids”
The Manufacturing Specific Object
“Solenoids”
contains the process output data for controlling the valves. A
value of 1 assigned to a bit in the Object data, indicates that the associated solenoid shall be energized,
whereas zero indicates that the power at the solenoid shall be off.
** These objects are available as Process Data Inputs or Outputs