Parker Hannifin Manufacturing Srl
user’s manual MDC
27
5
73B
Decimal parameters
Description field:
R
: read;
W
: write;
M
: memory;
K
: key parameter
Par.
Description
Field
Range
Def.
Res.
Pr0
Motor speed
: a read-only parameter
expressed in rpm; the Pr0 message is not
ever displayed on the screen. Instead, the
message indicating the status of the
converter is displayed.
R
± 15.000
[rpm]
0
1 rpm
Pr7
Main reference (read-only):
If b40.2=0 is
used, Pr7 is the reference for the speed
regulator. In some operating modes Pr7 can
be used as a reference for other values
(torque/acceleration) and in these cases Pr7
will be expressed in the most suitable unit
of measurement.
R
±9000
[rpm]
1 rpm
Pr13
Overspeed limit.
If the absolute value of
the motor speed exceeds the value set in
Pr13, b41.0 will be =1, Otherwise, it will be
= 0.
R/W
M
0÷13000
[rpm]
3500
1 rpm
Pr14
High speed limit.
If b40.7=0 and if the
difference of the speed of the motor and the
reference is less than Pr14 and greater than
Pr15, b41.1 will be = 1. Otherwise, it will
be 0. If b40.7 = 1 and if the motor speed is
less than Pr14 and greater than Pr15, b41.1
will be =1. Otherwise, it will be =0.
R/W
M
±13000
[rpm]
20
1 rpm
Pr15
Low speed limit.
If b40.7=0 and if the
difference of the speed of the motor and the
reference is less than Pr14 and greater than
Pr15, b41.1 will be =1. Otherwise, it will be
=0. If b40.7=1 and if the motor speed is less
than Pr14 and greater than Pr15, b41.1 will
be =1. Otherwise, it will be =0.
R/W
M
±13000
[rpm]
-20
1 rpm
Pr16
Integral gain of the speed regulator.
R/W,
M
0÷32767
120
1
Pr17
Damping of the speed regulator.
If
Pr16=0, Pr17 is the proportional gain of the
speed regulator.
R/W
M
0÷32767
2000
1
Pr18
Band width limiter.
Pr18 is used to set the
time constant of a first order filter placed on
the digital signal of the torque request. The
frequency of the filter cut will be:
1240/Pr18 Hertz.
R/W
M
1÷1000
[1=128
µsec]
3
1
Pr19
Peak torque.
This is the maximum torque
that the converter can supply to the motor.
It is expressed as a percentage of the peak
current of the motor multiplies to motor
constant torque.
R/W
M
0÷100.0
[%T
max
]
100.0
0.1%
Tmax
Pr20
DC bus voltage (read-only).
Displays the
value of the voltage present on the DC bus.
R
0÷850
[Volt]
1
Summary of Contents for MDC Series
Page 1: ...User s manual Rev 0 1 August 2012 MDC MotorNet DC www runcheng net www runcheng net...
Page 13: ...Parker Hannifin Manufacturing Srl user s manual MDC 13 3 3 Motor data...
Page 16: ...Parker Hannifin Manufacturing Srl user s manual MDC 16...
Page 17: ...Parker Hannifin Manufacturing Srl user s manual MDC 17...
Page 18: ...Parker Hannifin Manufacturing Srl user s manual MDC 18...
Page 22: ...Parker Hannifin Manufacturing Srl user s manual MDC 22 4 5 Hybrid cable Connection PSI MDC...