Parker EME
Conditions of utilization
192-120149 N08 June 2014
13
2.7.1.2
Conditions of utilization for cables / motor filter
Operation of the devices only with motor and feedback cables whose plugs contain a
special full surface area screening.
A motor output filter is required for motor cables >50m. Please contact us.
Shielding connection of the motor cable
The cable must be fully-screened and connected to the Compax3 housing. Use the
cable clamps/shield connecting terminals furnished with the device.
The shield of the cable must also be connected with the motor housing. The fixing
(via plug or screw in the terminal box) depends on the motor type.
< 100 m
Corresponding to the specifications of the terminal clamp with a temperature range
of up to 75°C.
Signal lines and power lines should be installed as far apart as possible.
Signal lines should never pass close to excessive sources of interference (motors,
transformers, contactors etc.).
Do not place mains filter output cable parallel to the load cable.
2.7.1.3
Additional conditions of utilization
Operation with standard motors.
Use only with aligned controller (to avoid control loop oscillation).
Connect the filter housing and the device to the cabinet frame, making sure that the
contact area is adequate and that the connection has low resistance and low
inductance.
Never mount the filter housing and the device on paint-coated surfaces!
Make sure to use only the accessories recommended by Parker
Connect all cable shields at both ends, ensuring large contact areas!
This is a product in the restricted sales distribution class according to EN
61800-3. In a domestic area this product can cause radio frequency
disturbance, in which case the user may be required to implement appropriate
remedial measures.
Motor and Feedback
cable:
Compax3H motor
cable
Feedback cable
Compax3S, Compax3H &
Compax3F:
Cable
Cable installation:
Motors:
Control:
Grounding:
Accessories:
Warning: