TWP/TWB200 – TWP/TWB9000
47
MODBUS REGISTER MAP (CONT’D)
Address
R/W
Description
Notes
10046
R
Output - Right Pre-Exhaust Valve
Right pre-exhaust valve is open
(Only dryers with pre-exhaust valves)
10047
R
Output - Left Exhaust Valve
Left Exhaust valve is open
10048
R
Output - Right Exhaust Valve
Right Exhaust valve is open
10049
R
Output - Open Left Inlet Valve
Left Inlet Valve is open (Dual acting Inlet valves only)
10050
R
Output - Open Right Inlet Valve
Right Inlet Valve is open (Dual acting Inlet valves only)
10051
R
Output - Close Left Inlet Valve
Left Inlet Valve is Closed
10052
R
Output - Close Right Inlet Valve
Right Inlet Valve is Closed
10066
R
Input - Sensor Power Sense
1 = sensor power present
0 = blown fuse or missing power
10067
R
Input - Emergency Stop Switch
1 = Normal switch position (No Emergency Stop )
0 = Emergency Stop Pressed
10068
R
Input - Blower Overload
1 = Blower Overload (Blower Models only)
10069
R
Input - Blower Flow Switch
1 = Blower Flow Switch Closed (Active) (Blower Models only)
10071
R
Input - Drain Switch #1
1 = drain switch closed (Demand drains only)
10072
R
Input - Drain Switch #2
1 = drain switch closed (Demand drains only)
10073
R
Input - Over-temp Sense
1 = Over-temp module normal operation
0 = Over-temp module has tripped on high temperature.
Heaters are disabled
10074
R
Input - Output Power Sense
1 = Output power is present,
0 = Blown fuse or missing power
10078
R
Input - Run/Stop Switch
1 = External Run/Standby Switch set to Standby Position
10079
R
Input - Remote Alarm Reset
1 = External contact closure resets Alarms and Restart Dryer
10081
R
Alarm - Left Blowdown
see separate alarm chart for details
10082
R
Alarm - Right Blowdown
see separate alarm chart for details
10083
R
Alarm - Left Repressurization
see separate alarm chart for details
10084
R
Alarm - Right Repressurization
see separate alarm chart for details
10085
R
Alarm - High Purge Temperature
see separate alarm chart for details
10086
R
Alarm - Low Purge Temperature
see separate alarm chart for details
10087
R
Alarm - High Over Temperature
see separate alarm chart for details
10089
R
Alarm - Left Muffler
see separate alarm chart for details
10090
R
Alarm - Right Muffler
see separate alarm chart for details
10091
R
Alarm - Low Purge Pressure
see separate alarm chart for details
10092
R
Alarm - Inlet Temperature
see separate alarm chart for details
10093
R
Alarm - Inlet Pressure
see separate alarm chart for details
10094
R
Alarm - High Dewpoint
see separate alarm chart for details
10095
R
Alarm - Pre-filter
see separate alarm chart for details
10096
R
Alarm - After-filter
see separate alarm chart for details
10097
R
Alarm - Blower Motor Overload
see separate alarm chart for details
10100
R
Alarm - Blower Flow Switch
see separate alarm chart for details
10101
R
Alarm - Drain #1 Switch
see separate alarm chart for details
10102
R
Alarm - Drain #2 Switch
see separate alarm chart for details
10103
R
Alarm - Aux Sensor Input #1 Low
see separate alarm chart for details
10104
R
Alarm - Aux Sensor Input #1 High
see separate alarm chart for details
Summary of Contents for Airtek TWB1000
Page 1: ...1 Externally Heated Blower Purge Desiccant Dryers User Manual Models TWP TWB200 TWP TWB9000...
Page 9: ...TWP TWB200 TWP TWB9000 9 TWP Desiccant Dryer Operation TWB Desiccant Dryer Operation...
Page 10: ...TWP TWB200 TWP TWB9000 10 FLOW SCHEMATIC MODELS TWP200 300 DWG FS11682 Rev...
Page 11: ...TWP TWB200 TWP TWB9000 11 FLOW SCHEMATIC MODELS TWP400 800 DWG FS11683 Rev...
Page 12: ...TWP TWB200 TWP TWB9000 12 FLOW SCHEMATIC MODELS TWP1000 1500 DWG FS11684 Rev...
Page 13: ...TWP TWB200 TWP TWB9000 13 FLOW SCHEMATIC MODELS TWP2000 9000 DWG FS11685 Rev...
Page 14: ...TWP TWB200 TWP TWB9000 14 FLOW SCHEMATIC MODELS TWB200 800 DWG FS11686 Rev...
Page 15: ...TWP TWB200 TWP TWB9000 15 FLOW SCHEMATIC MODELS TWB1000 1500 DWG FS11687 Rev...
Page 16: ...TWP TWB200 TWP TWB9000 16 FLOW SCHEMATIC MODELS TWB2000 9000 DWG FS11688 Rev...
Page 17: ...TWP TWB200 TWP TWB9000 17 WIRING DIAGRAM STANDARD CONTROLLER...
Page 18: ...TWP TWB200 TWP TWB9000 18 WIRING DIAGRAM STANDARD CONTROLLER...
Page 19: ...TWP TWB200 TWP TWB9000 19 WIRING DIAGRAM STANDARD CONTROLLER...
Page 20: ...TWP TWB200 TWP TWB9000 20 WIRING DIAGRAM STANDARD CONTROLLER...
Page 21: ...TWP TWB200 TWP TWB9000 21 PANEL LAYOUT STANDARD CONTROLLER...
Page 38: ...TWP TWB200 TWP TWB9000 38 Service Screen...
Page 71: ...TWP TWB200 TWP TWB9000 71...