![Parker AC650V Series Product Manual Download Page 52](http://html1.mh-extra.com/html/parker/ac650v-series/ac650v-series_product-manual_3771557052.webp)
Programming Your Application
6-20
650V AC Drive
400V Build Power Dependent Defaults
Frame 3
Parameter
Function Block
Tag
POWER
MOTOR DATA
1158
3.00 kw
4.00 kw
5.50 kw
7.50 kw
MOTOR CURRENT
MOTOR DATA
64
6.80 A
9.00 A
12.00 A
16.00 A
MAG CURRENT
MOTOR DATA
65
2.36 A
3.36 A
3.39 A
4.38 A
NAMEPLATE RPM
MOTOR DATA
83
1420.0 RPM
1420.0 RPM
1445.0 RPM
1450.0 RPM
MOTOR VOLTAGE
MOTOR DATA
1160
400.0 V
400.0 V
400.0 V
400.0 V
POWER FACTOR
MOTOR DATA
242
0.8
0.8
0.8
0.8
STATOR RES
MOTOR DATA
119
2.0620 ohms
2.0620 ohms
1.3625 ohms
1.0545 ohms
LEAKAGE INDUC
MOTOR DATA
120
43.76 mH
43.76 mH
43.37 mH
33.57 mH
MUTUAL INDUC
MOTOR DATA
121
175.03 mH
175.03 mH
173.48 mH
134.27 mH
ROTOR TIME CONST
MOTOR DATA
1163
136.75 ms
136.75 ms
276.04 ms
303.65 ms
BRAKE POWER
DYNAMIC BRAKING
78
0.2 kW
0.2 kW
0.5 kW
0.5 kW
FREQUENCY
INJ BRAKING
577
9.0 Hz
9.0 Hz
9.0 Hz
9.0 Hz
DEFLUX TIME
INJ BRAKING
710
0.5 s
0.5 s
0.5 s
0.5 s
BASE VOLTS
INJ BRAKING
739
100.00 %
100.00 %
100.00 %
100.00 %
DC LEVEL
INJ BRAKING
581
3.0 %
3.0 %
3.0 %
3.0 %
DC PULSE
INJ BRAKING
579
2.0 s
2.0 s
2.0 s
2.0 s
FINAL DC PULSE
INJ BRAKING
580
1.0 s
1.0 s
1.0 s
1.0 s
FIXED BOOST
FLUXING
107
5.00%
5.00%
5.00%
5.00%
ACCEL TIME
REFERENCE RAMP
258
10.0 s
10.0 s
10.0 s
10.0 s
DECEL TIME
REFERENCE RAMP
259
10.0 s
10.0 s
10.0 s
10.0 s
DEFLUX DELAY
PATTERN GEN
100
2.0 s
2.0 s
2.0 s
2.0 s
SEARCH VOLTS
FLYCATCHING
573
9.00 %
9.00 %
9.00 %
9.00 %
SEARCH BOOST
FLYCATCHING
32
40.00 %
40.00 %
40.00 %
40.00 %
SEARCH TIME
FLYCATCHING
574
5.0 s
5.0 s
5.0 s
5.0 s
REFLUX TIME
FLYCATCHING
709
3.0 s
3.0 s
3.0 s
3.0 s
OVERLOAD
MOTOR DATA
1164
2.0
2.0
2.0
2.0
SPEED PROP GAIN
SPEED LOOP
1187
20
20
20
20
SPEED INT TIME
SPEED LOOP
1188
500. ms
500. ms
500. ms
500. ms
MOTOR CONNECTION MOTOR DATA
124
1 : STAR
1 : STAR
1 : STAR
1 : STAR
BRAKE RESISTANCE
DYNAMIC BRAKING
77
100
100
56
56
BOOST MODE
FLUXING
1058
1
1
1
1