Programming Your Application
6-4
650V AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::CTRL Menu
CONTROL MODE This parameter contains the main method of
motor control used by the drive
0=VOLTS/HZ
1=SENSORLESS VEC
0
NAMEPLATE RPM
M
This parameter contains the motor nameplate full-
load rated speed. This is the motor speed in rpm
at base frequency minus full load slip
0.1 to 30000.0 RPM product
code
dependent
FLY-CATCH
ENABLE
VF
Enables flycatching in Volts/Hz control mode when
TRUE. Allows the drive to catch a spinning load.
0=FALSE
1=TRUE
0
FLY-CATCH
ENABLE
SV
Enables flycatching in Sensorless Vector control
mode when TRUE. Allows the drive to catch a
spinning load.
0=FALSE
1=TRUE
0
SLIP COMP
ENABLE
VF
Slip compensation is operational when TRUE.
Eliminates motor speed variations under load
conditions in V/F Fluxing Mode when the correct
value for MAG CURRENT is entered into
S
CL14
0=FALSE
1=TRUE
0
STABILISATION
ENABLE
VF
Enables the stabilisation function when TRUE.
Eliminates light load speed variations in V/F
Fluxing Mode
0=FALSE
1=TRUE
1
VOLTAGE
CONTROL MODE
VF
NONE : no attempt is made to control the PWM
modulation depth for variations in dc link voltage
FIXED : the drive's output volts are maintained,
regardless of variations in the dc link voltage. The
drive's product code sets the default value for
demanded maximum output voltage (see MOTOR
VOLTAGE below)
AUTOMATIC : the drive performs controlled over-
fluxing during motor deceleration
0=NONE
1=FIXED
2=AUTOMATIC
0
BOOST MODE
F
VF
Determines the relationship between fixed boost
and terminal volts. There are two settings:
FALSE produces the terminal volts profile shown
below (with Auto Boost set to 0.0 %). In this mode
AUTO BOOST (CL08) should also be set to
provide optimum low speed performance.
TRUE emulates the terminal volts profile provided
by the Parker SSD Drives' 601 product. This allows
drop in replacement of the 601 by the 650V.
AUTO BOOST (CL08) has no effect in this
mode.
100%
BASE
Simple Mode (CL07 = 1)
Advanced Mode (CL07 = 0)
Output Frequency
Motor
Terminal
Volts
BOOST %
FIXED
FREQUENCY
0=FALSE
1=TRUE
1