8 Configuration
The option comms configuration is accessible through the keypad under the menu
Option Comms
,
through DSE Lite function block
Option Comms Config
or through the webserver following the path
Home
> Engineer > Communications > Option Comms
.
The AC20 EtherCAT option requires configuration of both communication parameters and process data
mapping.
8.1 Communication parameters
Keypad Menu Path
DSE-Lite Function Block
Webserver
The network parameters of the slave must be set to establish communication with master
.
•
The parameter
0691 COMMS REQUIRED
must be set to
EtherCAT.
•
The parameter
2566 MASTERMAPPING
must be set to
choose how process data mapping is
8.2 Process Data for detail)
Setup
Communication