Page 13
890SD Control Connections
•
Connect volt-free
contacts as required
•
RUN (maintained contact)
terminal X14/03 and
terminal X15/02
B
Sequencing
•
Connect a 10kΩ potentiometer at
terminal block X12 (Analog I/P 3)
High (CW):
terminal X12/08
Wiper:
terminal X12/04
Low (CCW):
terminal X12/01
•
Connect the shield to earth/ground
at the bottom ground bracket
A
Speed Reference
OR
•
External 2-wire speed reference
between
terminals X12/01(-) and X12/04(+)
•
Connect the shield to earth ground
at the bottom ground bracket
•
SPEED FEEDBACK
10V = ±100% speed
at terminal X12/0 6
•
TORQUE FEEDBACK
10V = ±200% torque
at terminal X12/07
•
ANALOG COMMON
0V at terminal X12/0 1
Analog
This is a basic connection diagram.
For more detailed information on control connections, refer to Appendix B.
•
DRIVE HEALTH
Relay dry contact
(24V rated) at
terminal X14/01 and
terminal X14/02
•
RUNNING
24V sourcing output
at terminal X15/08
•
ZERO SPEED
24V sourcing output
at terminal X15/09
•
DIGITAL COMMON
0V at terminal X14/04
Digital
The control terminals will accept a single wire of
size 1.5mm
2
/16AWG. For two wires per terminal,
use smaller gauge wire such as 0.5mm
2
/22AWG.
•
Connect motor thermal
switch or thermistor to
terminals X16/08 &
X16/09. Drive will trip
when the thermal switch
opens, or when the
thermistor resistance
exceeds 4k
Ω
maximum
(PTC Type A : IEC 34-11
Part 2)
•
If the motor does not
have a protective device
(thermistor), jumper
these terminals. The
drive needs the
thermistor inputs
connected for it to run.
C
Thermistor
Summary of Contents for 890 Series
Page 3: ...Page 2...
Page 23: ...Page 22 890SD Control Terminals...
Page 24: ...Page 23 Appendix C Electrical Ratings Notes for Electrical Ratings Tables...
Page 25: ...Page 24 Electrical Ratings 890SD Frame G 400V...
Page 26: ...Page 25 Electrical Ratings 890SD Frame H 400V...
Page 27: ...Page 26 Electrical Ratings 890SD Frame J 400V...