Page 17
Autotune
•
Ensure that MAX SPEED is greater than NAMEPLATE RPM for a successful autotune.
•
In the QUICK SETUP menu, set AUTOTUNE ENABLE to TRUE.
•
On the 890SD keypad select LOCAL mode. Set SETPOINT (LOCAL) to 0.0%.
•
Press the green RUN button. The drive will begin autotuning. The drive will stop without errors if
autotune is successful.
•
Go to SYSTEM::SAVE CONFIG::APPLICATION and UP arrow to save your settings.
This section is only for operating in Sensorless or Closed-loop Vector modes.
If the drive is in V/Hz mode, Autotune is unnecessary and will not Enable.
ROTATING AUTOTUNE
STATIONARY AUTOTUNE
Under QUICK SETUP, enter the exact MAG
CURRENT in Amps (from motor data)
Under Quick setup, set AUTOTUNE MODE to
STATIONARY
Is the motor uncoupled
from the load and free
to rotate without
causing problems?
YES
NO