Installation
A simplified installation is shown below. This installation is
not
EMC compliant. For European
installations and countries with EMC legislation refer to the 890 Engineering Reference Manual,
Appendix C.
KEY
B
Back-plate
C
Cubicle
D
Control Wiring terminals
G
Supply Protective Earth/Ground
K
Motor (M1, M2, M3)
L
3
∅
Power Supply Cable (L1, L2, L3)
N
Vent Kit with (optional) Drive Brake Unit
P
Fuse or Circuit Breaker
R
AC Line Choke
T
Auxiliary Supply
V
External Fan (Frame J)
* Permanent Earthing
Each unit must be
permanently earthed
according to EN 50178. For permanent
earthing, EN 50178 states that:
A cross-section conductor of at least
10mm² is required. This can be achieved
either by using a single conductor (PE)
or by laying a second conductor though
separate terminals (PE2 where provided)
and electrically in parallel.
Conductors must be sized in
accordance with Local Wiring
Regulations which always take
precedence.
As a guide, refer to the Input Current for
the drive given in the Electrical Ratings
tables.
Summary of Contents for 890 Series
Page 3: ...Page 2...
Page 23: ...Page 22 890SD Control Terminals...
Page 24: ...Page 23 Appendix C Electrical Ratings Notes for Electrical Ratings Tables...
Page 25: ...Page 24 Electrical Ratings 890SD Frame G 400V...
Page 26: ...Page 25 Electrical Ratings 890SD Frame H 400V...
Page 27: ...Page 26 Electrical Ratings 890SD Frame J 400V...