Current Calibration
Current Calibration is achieved using the BCD switches SW2, 3 and 4 where SW2 represents the
'Tens'; SW3 represents the 'Units' and SW4 represents the 'Tenths'. Thus a 16.5 amp calibration
is achieved by setting switch SW2 to 1, SW3 to 6, and SW4 to 5.
Please note that incorrect adjustment of these switches will cause excessive current to flow
which may cause damage to the motor and the controller. The absolute maximum setting
which can be set is 39.9 amps, this exceeds the Maximum Controller rating in all builds.
POTENTIOMETERS
P1 Ramp Up Rate Rotate Clockwise for Faster Acceleration to
Set Speed.
(Linear :- 1 to 40 seconds)
Default
Setting:
Midway
540/1 P1
P2 Ramp Down
Rate
Rotate Clockwise for Faster Deceleration to
Set Speed.
(Linear :- 1 to 40 seconds)
Midway
540/1 P2
P3 Speed Loop
Proportional
Optimises Speed Loop Stability by
increasing gain.
Midway
540/1 P5
P4 Speed Loop
Integral
Optimises Speed Loop Stability by
increasing integral time constant.
Midway
540/1 P6
P5 I Limit
Rotate Clockwise to increase Maximum
Output Current.
With no additional connection to Torque /
Current Limit Terminal T7, the Upper Limit
is 110%. To achieve the 150% maximum
connect T7 to +7.5V.
90%
Clockwise
540/1 P7
P6 Current Loop
Proportional
Optimises Current Loop Stability by
increasing gain.
Midway
540/1 P8
P7 Current Loop
Integral
Optimises Current Loop Stability by
increasing integral time constant.
Anti-
Clockwise
540/1 P9
P8 IR
Compensation
Optimises speed regulation against load
change when using Armature Voltage
Feedback. Rotate Clockwise to increase
compensation and reduce regulation.
(Excessive adjustment may lead to
instability)
Anti-
Clockwise
P9 DO NOT USE Pending Change.
P10 Maximum
Speed
Controls Maximum Motor Speed. Rotate
clockwise to increase maximum speed.
Midway
540/1
P10
P11 Zero Speed
Offset
Adjusts Zero for Zero Speed Setpoint.
Approx-
imately
Midway
540/1 P3
P12 Zero Speed
Sense
Threshold
Adjusts the Zero Speed sense Level for the
Zero Speed relay and Standstill Logic if
selected.
Anti-
Clockwise
540/1 P4
TABLE 4.3 Customer Adjustments.