4-1
Setting up & Commissioning
514C Product Manual
Chapter 4
Setting-Up & Commissioning
OPTION SWITCHES
Speed Feedback
SW1/1
SW1/2
FEEDBACK VOLTAGE
OFF
ON
10 - 25V
USE P10 TO TRIM
ON
ON
25 - 75V
MAXIMUM SPEED
OFF
OFF
75 - 125V
TO REQUIRED
ON
OFF
125 - 325V
VALUE
TABLE 4.1 Full speed tachogenerator/armature feedback voltage.
Example:
(a) Customer wishes to run motor at 1500rpm with a 60V/1000rpm tachogenerator.
Feedback voltage = 90V.
From Table 4.1 set SW1 OFF SW2 OFF adjust P10 to give desired speed.
(b) Customer wishes to run motor at 2000rpm with 320V armature.
Feedback voltage = 320V
From Table 4.1 set SW1 ON SW2 OFF adjust P10 to give desired speed.
Note:- It is necessary to set these switches for both tachogenerator and armature voltage feedback.
General Purpose Switches
SW1/3
Speed Feedback
(OFF) Tachogenerator Feedback for Speed Control.
(ON) Armature Voltage Feedback for Speed Control.
SW1/4
Zero Output
(OFF) Zero Speed Output.
(ON) Zero Setpoint Output.
SW1/5
Current Meter
(OFF) Bipolar Output.
(ON) Modulus Output.
SW1/6
Ramp Isolate
(OFF) Ramp Connected.
(ON) Ramp Isolated.
SW1/7
Standstill Logic
(OFF) Disabled.
(ON) Enabled.
SW1/8
Current Demand
(OFF) T18 = Current Demand Input.
(ON) T18 = Current Demand Output.
SW1/9 Contactor Drop Out
on Over-Current
(OFF) Contactor Drops Out on Over Current trip
(ON) Contactor does not Drop Out on Over Current trip
SW1/10 Setpoint Comparator. (OFF) Total Setpoint.
(ON) Ramped Setpoint Input.
Default switch settings are
SW1/1 = Off SW1/2 = On SW1/3 = On SW1/4 = Off SW1/5 = Off SW1/6 = Off
SW1/7 = Off SW1/8 = On SW1/9 = Off SW1/10 = Off