3-4
Setting up & Commissioning
514C Product Manual
Function Rating
Cable Size
Fuse Isolator Kit Fuse Rating Parker Part
No.
514C-04 Supply 6A
1.5mm
2
/16AWG LA057605U012 12A fuse CH390123
Motor
4A
1.5mm
2
/16AWG
(10A U.S.)
Ground
1.5mm
2
/16AWG
514C-08 Supply 12A
2.5mm
2
/14AWG LA057605U016 16A fuse
(15A U.S.)
CH390163
Motor
8A
2.5mm
2
/14AWG
Ground
2.5mm
2
/14AWG
514C-16 Supply 24A
6mm
2
/10AWG LA057605U032 32A fuse
(30A U.S.)
CH390323
Motor
16A
6mm
2
/10AWG
Ground
6mm
2
/10AWG
514C-32 Supply 48A
16mm
2
/6AWG LA057605U050 50A fuse
(60A U.S.)
CH390054
Motor
32A
16mm
2
/6AWG
Ground
16mm
2
/6AWG
ALL
Field
3A
1.5mm
2
/16AWG LA054664
10A
CH230014
TABLE 3.1 Recommended Cable Sizes.
Note:- The cable sizes shown are based on a Form Factor of 1.5 and an overload allowance of
110% (giving a multiplier of 1.65), they are selected for the notional rating of each controller.
Smaller cable may be used if the controller is calibrated at a lower current level.
Terminal Tightening Torques
Control
0.45 Nm
0.33 lbf-ft
4.0 lbf-in
Auxiliary Supply & Field
0.5 Nm
0.375 lbf-ft
4.5 lbf-in
Power
2.7 Nm
2 lbf-ft
24 lbf-in
Earth (Grounding)
7.1 Nm
5.25 lbf-ft
63 lbf-in