Pre-Installation Planning
2-3
514C Product Manual
TERMINAL
FUNCTION
DESCRIPTION
NOTES
T18 Current Demand
Input / Output
Analogue Input or Output:
SW1/8 'ON' = Current Demand
Output.
SW1/8 'OFF' = Current Demand Input.
0 to
7.5V = 0 to
150% Current.
5mA output
S/C protected approx.
100 kohm.
T19 Health Output
Digital Output,
+24V = Healthy.
50mA Source
Short Circuit Protected.
T20 Enable Input
Digital Input to Enable Controller.
+10V to +24V to Enable.
0V to Disable.
100k approx.
T21 Inverted Setpoint
Sum Output
Analogue Output,
0 to -10V = 0 to 100% Forward Speed.
5mA output
S/C protected.
T22 Thermistor /
Microtherm Input
Motor Thermistor or Microtherm Sensor
<200 ohm to 0V = Normal.
>1800 ohm to 0V= Overtemperature.
5k approx.
T23 Zero Speed Output
/Zero Setpoint
Output
Digital Output,
+24V = Stopped/Zero Setpoint.
0V = Running/Non zero setpoint.
50mA Source
Short Circuit Protected.
T24 +24V
+24V Supply Output.
20mA. For use on the
drive only.
CAUTION
The +24v supply from the drive (terminal T24) is for use with the drive only. It
should be used with the RUN circuit (terminal 5) to control the drives internal
relay to switch the contactor and can be used with the ENABLE circuit (terminal
T20).
DO NOT use the +24v supply to power any circuit or device external to the
drive. This includes external relays, PLC’s, and any other equipment.
Using the +24v external to the drive could result in drive malfunction or damage,
damage to connected equipment, and could endanger personnel.