3 / 6
SPE004-100
5 Control
QS
Main power switch
UP button: press to increase the value of a selected
parameter
DOWN button: press to reduce the value of a selected
parameter
esc
ESC button :returns to the previous level
set
SET button : one single press to see the alarms, press
for more seconds to enter Menu (Service e Factory)
(lit) Dew point correct
(Flashing) warning dew point high/low
(off) alarm dew point
(lit) Condensate drain ON
(off) Condensate drain OFF
(lit) Multiple alarms
(Flashing) Warning “maintenance”
Degree
5.1 Parameter settings
There are two levels of protection for parameters:
a) User (U): with immediate access,
User-changeable;
b) Password protected Factory/Service (F/S): password required
for access;
Factory-set parameters.
Condensate drain
There are two operating modes:
a) TIMED (TIm) - with draining at intervals and settable time;
in this confi guration keep pressed
to force the drain to
work;
b) EXTERN (CON) - if there is an external drain.
For chosing the set proceed as follows::
Press button
set
over 5 seconds to enter on menu U.
Using buttons
and
select “CHd” and press
set
to con-
fi rm.
Using buttons
and
select “TIm” or “CON” .
Press
esc
to confi rm and exit.
In the same way it is possible to change interval and discharge
times of the drain.
Parameter table
Code Defi nition
De-
fault
Min
Max.
dON
Time ON Drain
5
1
60
dOFF
Time OFF Drain
120
20
2700
CHd
Confi guration drain
TIm
TIm
CON
ALC
relay alarm/warning
ON = relay energised for
alarms/warnings
OFF = relay energised only
alarms
ON
OFF
ON
Flow Chart
set
Y
Y
Y
>5 sec.
Menu
User
CHd
set
Y
TIm
Y
CON
Y
esc
Alarms/Warnings
When an alarm is ON, the “alarm/warning code” fl ashing on dis-
play.
Multiple alarms appear in sequence. The symbol appears
.
In any case you can press
set
to see the alarms, using the but-
tons
and
.
Code
Description alarm / warning
---
No alarms present
HdP
Alarm High Dew point
LdP
Alarm Low Dew Point
DSE
Alarm sensor B1 faulti/disconnected
H
Warning High Dew point
L
Warning Low Dew point
Press
esc
to exit.
Flow Chart
set
Y
Y
Y
<5 sec.
Code 1
Alarm
Warning
esc
Code 2
Alarm
Warning
Code....
Alarm
Warning
Y
Y
esc
esc
.
Summary of Contents for StarlettePlus-E Series
Page 2: ......
Page 8: ...Italiano 6 6 SPE004 100 ...
Page 14: ...English 6 6 SPE004 100 ...
Page 20: ...Español 6 6 SPE004 100 ...
Page 44: ...Svenska 6 6 SPE004 100 ...
Page 50: ...Suomi 6 6 SPE004 100 ...
Page 56: ...Norsk 6 6 SPE004 100 ...
Page 62: ...Nederlands 6 6 SPE004 100 ...
Page 68: ...Dansk 6 6 SPE004 100 ...
Page 80: ...Česky 6 6 SPE004 100 ...
Page 86: ...Magyar 6 6 SPE004 100 ...
Page 112: ... 8 8 WIRING DIAGRAM 14 SPE004 100 Ĭ A1 Ĭ Option ...
Page 116: ......
Page 117: ......