background image

   English

  ICE003-005 

2 / 6

2 Introduction

Th

  ese water coolers are monoblock units for the production of cooled 

water in a closed circuit.
Th

  e fan, pump and compressor motors are equipped with a thermal 

protector that protects them against possible overheating.

2.1 Transport

Th

  e packed unit must remain:

a)  Upright;
b)  Protected against atmospheric agents;
c)  Protected against impacts.

2.2 Handling

Use a fork-lift  truck suitable for the weight to be lift ed, avoiding any 
type of impact

2.3 Inspection

a)  All the units are assembled, wired, charged with refrigerant and oil 

and tested in the factory;

b)  On receiving the machine check its condition: immediately notify 

the transport company in case of any damage; 

c)  Unpack the unit as close as possible to the place of installation.

2.4 Storage

a)  Keep the unit packed in a clean place protected from damp and bad 

weather.

b)  Do not stack the units;
c)  Follow the instructions given on the package.

3 Installation

For correct installation, follow the instructions given in par.7.2 

and 7.6.

!

 

Liquids to be chilled

Th

  e liquids to be chilled must be compatible with the materials used.

Examples of liquids used are water or mixtures of 

water and ethylene 

or propylene glycols.

Th

  e liquids to be chilled must not be fl ammable. 

If the liquids to be chilled contain hazardous substances (e.g. ethylene/
propylene glycol), any liquid discharged from a leakage area must be 
collected, because it is harmful to the environment.  When draining 
the hydraulic circuit, comply with the current regulations and do not 
disperse the contents in the environment.

3.1 Operating 

space

Leave a space of 1.5 m around the unit. 
Leave a space of at least 2 metres above the refrigerator in models with 
vertical emission of condensation air..

3.2 Versions

Axial fans (A)

Do not create cooling air recirculation situations. 
Do not obstruct the ventilation grilles.
Th

  e ducting of extracted air is not recommended for versions with 

axial fans.

3.3 Water 

circuit

3.3.1. 

Checks and connection

Before connecting the chiller and fi lling the water circuit, check 

that all the pipes are clean. If not, wash them out thoroughly. 

If the plumbing circuit is of the closed type, under pressure it is 

advisable to install a safety valve set to 6 bar. 

Always install mesh fi lters on the water inlet and outlet pipelines.

If the hydraulic circuit is intercepted by automatic valves, protect 

the pump with an anti-hammering system.

If the hydraulic circuit is emptied for shut-down periods we 

recommend that you add lubricating fl uid to the pump’s impeller to 
avoid the risk of blockage when it is re-started.    In case the impeller is 
blocked then you should unblock it manually.
Remove the rear cover of the pump and carefully turn the plastic fan.   
If the impeller is stuck then remove the fan and turn the impeller shaft  
directly.    Aft er un-blocking the impeller re-assemble the fan and 
cover.

Preliminary checks

1)  Check that any shut-off  valves in the water circuit are open.
2)  In the case of a closed water circuit, check that an expansion tank 

of suitable capacity has been installed. See paragraph 3.3.3..

Connection

1)  Connect the water cooler to the inlet and outlet piping, using the 

special connections located on the back of the unit.
We recommend the use of fl exible unions to reduce system rigidity.

2)  Fill the water circuit using the fi tting provided on the rear of the 

chiller(

).

3)  Th

  e tank is equipped with a breather valve that should be operated 

manually when fi lling the tank. Also, if the hydraulic circuit has high 
points, install a vent valve at the highest points.

4)  We recommend that taps are installed on the inlet and outlet pipes, 

so that the unit can be excluded for maintenance when necessary.

Subsequent checks

1)  Check that the tank and the circuit are completely full of water and 

that all the air has been expelled from the system.

2)  Th

  e water circuit must always be kept full. For this reason, carry 

out periodic checks and top the circuit up if necessary, or install an 
automatic fi lling kit.

3.3.2. 

Water and ethylene glycol

If installed outdoors or in an unheated indoor area, it is possible that 
the water in the circuit may freeze if the system is not in operation dur-
ing the coldest times of the year.
To avoid this hazard:

a)  Equip the chiller with suitable antifreeze protection devices, avail-

able from the manufacturer as optional accessories;

b)  Drain the system via the drain valve if the chiller is to remain idle 

for a prolonged period;

c)  Add an appropriate quantity of antifreeze to the water in circula-

tion (see table).

Sometimes the temperature of the outlet water is so low as to require 
the addition of ethylene glycol in the following percentages.

Outlet water

temperature  [°C]

Ethylene glycol

(% vol.)

Ambient

temperature

4

5

-2

2

10

-5

0

15

-7

-

20

-10

-

25

-12

-

30

-15

3.3.3. Expansion 

tank

To avoid the possibility of an increase or decrease in the volume of the 
fl uid due to a signifi cant change in its temperature causing damage to 
the machine or the water circuit, we recommend installing an expan-
sion tank of suitable capacity.
Th

  e expansion tank must be installed on intake to the pump on the rear 

connection of the tank.
Th

  e minimum volume of an expansion tank to be installed on a closed 

circuit can be calculated using the following formula:
V=2 x Vtot x (Pt min - P t max)
where
Vtot= vol. circuit total (in litres)
P t min/max= specifi c weight at the minimum/maximum temperature 
reached by the water [kg/dm3].
Th

 e specifi c weight values at diff erent temperatures for glycol percent-

age values are given in the table.

%

glicol

Temperature [°C]

-10

0

10

20

30

40

50

0%

1.0024 1.0008 0.9988 0.9964 0.9936 0.9905 0.9869

10%

1.0177 1.0155 1.0130 1.0101 1.0067 1.0030 0.9989

20%

1.0330 1.0303 1.0272 1.0237 1.0199 1.0156 1.0110

30%

1.0483 1.0450 1.0414 1.0374 1.0330 1.0282 1.0230

!

 

 Caution: When fi lling the system, take into account the capac-

Summary of Contents for Hyperchill ICE003

Page 1: ...ICE003 ICE005 Hyperchill 50Hz DATE 15 01 2015 Rev 18 CODE 398H271640 IT Manuale d uso EN User Manual ES Manual de uso DE Benutzer Handbuch ...

Page 2: ......

Page 3: ...NE Il costruttore si riserva il diritto di modificare le informa zioni contenute nel presente manuale senza alcun preavviso Ai fini di una completa ed aggiornata informazione si raccomanda all utente di consul tare il manuale a bordo unità 1 4 Rischi residui L installazione l avviamento lo spegnimento la manutenzione della macchina devono essere tassativamente eseguiti in accordo con quan to ripor...

Page 4: ...tola in plastica Se l albero risultasse ancora bloccato rimuovere la ventola e agire direttamente sull albero Una volta sbloccata la girante riposizionare ventola e coperchio Controlli preliminari 1 Controllare che le eventuali valvole di intercettazione del circuito idraulico siano aperte 2 Se il circuito idraulico è di tipo chiuso controllare che sia stato in stallato un vaso d espansione di cap...

Page 5: ...eno IP2Xo IPXXB 4 Installare sulla linea di alimentazione elettrica del refrigeratore un interruttore automatico con differenziale RCCB IDn 0 3A della portata massima indicata nello schema elettrico di riferimento con potere di interruzione adeguato alla corrente di corto circuito esistente nella zona d installazione della macchina La corrente nominale In di tale magnetotermico deve essere uguale ...

Page 6: ...nare unità di misura 5 C 0 4 4 3 Parametro regolatore PARAMETRO CODICE TIPO DEFAULT Differenziale di regolazione isteresi 0 0 5 C F rd F 3 4 4 4 Parametri compressore PARAMETRO CODICE TIPO DEFAULT Ritardo partenza compressore all accensione strumento min C0 C 0 Tempo min tra due accensioni successive del compress min CI C 6 Tempo min di spegnimento del compressore min C2 C 0 Tempo min di funzionam...

Page 7: ... della macchina in caso contrario i danni provocati da errata carica di refrigerante non verranno riconosciuti in garanzia 5 2 Manutenzione preventiva Per garantire nel tempo la massima efficienza ed affidabilità del chiller eseguire a Z ogni 4 mesi pulizia alette condensatore e verifica assorbimento elettrico compressore entro valori di targa b Z ogni 3 anni installazione kit manutenzione ogni 3 ...

Page 8: ...AMBIENTE SOTTO IL VALO RE LIMITE DICHIARATO PRESSOSTATO ROTTO O STARATO SOSTITUIRE IL PRESSOSTATO FILTRO REFRIGERANTE INTASATO SOSTITUIRE IL FILTRO ALETTE DEL CONDENSATORE SPORCHE PULIRE LE ALETTE DEL CONDENSATORE SUPERFICIE DEL CONDENSA TORE OSTRUITA LIBERARE LA SUPER FICIE FRONTALE DEL CONDENSATORE PORTATA ACQUA INSUFFICIENTE AUMENTARE LA PORTATA DEL FLUIDO DA RAFFREDDARE COMPONENTI COMPRESSORE ...

Page 9: ...manufacturer reserves the right to modify this manual at any time For the most comprehensive and updated information the user is advised to consult the manual supplied with the unit 1 4 Residual risks The installation start up stopping and maintenance of the machine must be performed in accordance with the information and instruc tions given in the technical documentation supplied and always in su...

Page 10: ...y After un blocking the impeller re assemble the fan and cover Preliminary checks 1 Check that any shut off valves in the water circuit are open 2 In the case of a closed water circuit check that an expansion tank of suitable capacity has been installed See paragraph 3 3 3 Connection 1 Connect the water cooler to the inlet and outlet piping using the special connections located on the back of the ...

Page 11: ...aker must be equal to the FLA with an intervention curve type D 5 Max grid impedance value 0 274 ohm Subsequent checks Check that the machine and the auxiliary equipment are earthed and protected against short circuit and or overload Once the unit has been connected and the upstream main switch closed thereby connecting the power supply to the machine the voltage in the electrical circuit will rea...

Page 12: ...uccessive compres sor start ups min CI C 6 Minimum compressor Off time min C2 C 0 Minimum compressor On time min C3 C 0 4 5 Parameter management 4 5 1 Temperature setting see fig 1 1 Press button B SET the message SET will appear followed by the set value blinking 2 Change the value using the up and down arrow buttons A and C then press button B SET to exit and save The temperature set point has n...

Page 13: ...n otherwise any damage caused by incorrect refrigerant charging will not be covered by the warranty 5 2 Preventive maintenance To guarantee lasting maximum chiller efficiency and reliability carry out a Z every 4 months clean the condenser fins and make sure com pressor electrical absorption is within the dataplate values b Z Every 3 years installation of kit for maintenance every 3 years par 7 4 ...

Page 14: ...URE TO BELOW THE SPECIFIED LIMIT PRESSURE SWITCH BROKEN OR WRONGLY CALIBRATED REPLACE PRESSURE SWITCH REFRIGERANT FILTER CLOGGED REPLACE THE FILTER CONDENSER FINS DIRTY CLEAN THE FINS OF THE CONDENSER CONDENSER SURFACES CLOGGED CLEAR THE FRONT SURFACE OF THE CONDENSER INSUFFICIENT WATER FLOW INCREASE THE FLOW RATE OF THE FLUID TO BE COOLED COMPRESSOR COMPONENTS DETERIORATED REPAIR OR REPLACE COMPR...

Page 15: ... componentes ATENCIÓN El fabricante se reserva el derecho de modificar sin previo aviso la información de este manual Para que la información resulte completa se recomienda al usuario consultar el manual a pie de máquina 1 4 Riesgos residuales Las operaciones de instalación puesta en marcha apagado y mantenimiento del equipo deben realizarse de total confor midad con lo indicado en la documentació...

Page 16: ...terior de la bomba y gire suavemente el ventilador de plástico Si el eje siguiera bloqueado quite el ventilador y actúe direc tamente en el eje Una vez desbloqueado el rodete vuelva a colocar el ventilador y la tapa Controles preliminares 1 Cerciorarse de que las válvulas de corte del circuito hidráulico estén abiertas 2 Si el circuito hidráulico es cerrado controlar que se haya instalado un vaso ...

Page 17: ... un interruptor automático con diferencial de RCCB IDn 0 3A la capacidad máxima indicada en el esquema eléctrico de referencia y un poder de corte adecuado a la corriente de cortocircuito existente en el lugar de instalación La corriente nominal In de dicho magnetotérmico debe ser igual a FLA y la curva di intervención de tipo D 5 Valor máximo de la impedancia de red 0 274 ohm Controles sucesivos ...

Page 18: ...Selección de la unidad de me dida 5 C 0 4 4 3 Parámetros del regulador PARÁMETRO CÓDIGO TIPO PREDET Diferencial de regulación histéresis 0 0 5 C F rd F 3 4 4 4 Parámetros del compresor PARÁMETRO CÓDIGO TIPO PREDET Retardo arranque del compre sor al encenderse el instrumento min C0 C 0 Tiempo mínimo entre dos en cendidos sucesivos del compre sor min CI C 6 Tiempo mínimo de inactividad del compresor...

Page 19: ...nómalo del equipo de lo contrario los daños causados por una carga incorrecta de refrigerante no serán reconocidos en garantía 5 2 Mantenimiento preventivo Para garantizar la máxima eficacia y fiabilidad del refrigerador hay que a Z ocada 4 meses climpiar las aletas del condensador y contro lar que la absorción de corriente del compresor esté dentro de los valores nominales b Z ada 3 años instalac...

Page 20: ...BIENTE AL CAMPO DE FUNCIONAMIENTO INDICA DO PRESOSTATO ROTO O DESCALIBRADO CAMBIAR EL PRESOSTATO FILTRO REFRIGERANTE ATASCADO SUSTITUIR EL FILTRO ALETAS DEL CONDENSADOR SUCIAS LIMPIAR LAS ALETAS DEL CONDENSADOR SUPERFICIE DEL CONDENSA DOR OBSTRUIDA LIBERAR LA SUPER FICIE FRONTAL DEL CONDENSADOR CAUDAL DE AGUA INSUFICIENTE AUMENTAR EL CAU DAL DEL FLUIDO A REFRIGERAR COMPONENETES COMPRESOR DETERIORA...

Page 21: ... Änderung an der Verpackung entstandene Schäden Der Anwender hat sich zu vergewissern dass die für die Auswahl der Anlage gelieferten Spezifikationen und oder deren Bauteile und oder Optionen für die korrekte bzw in vernünftiger Weise vorhersehbare Nutzung der Anlage bzw der Bauteile ausreichen ACHTUNG Der Hersteller behält sich das Recht vor die in dem vorliegenden Handbuch enthaltenen Informatio...

Page 22: ...ich die Installation eines auf 6 Bar geeichten Sicherheitsven tils Y An den Wassereinlauf und Wasserauslaufleitungen sollten stets geeignete Siebfilter installiert werden Y Wird der Wasserkreis durch automatisch ansprechende Ventile gesperrt ist die Pumpe durch geeignete Wasserschlag Schutzsysteme zu schützen Y Falls der Kreislauf vor einem längeren Stillstand der Maschine entleert wird ist es ang...

Page 23: ...d der Neutralleiter geerdet sein in eigener Kabine TN Anlage oder vonseiten des Stromnetzbetreibers TT Anlage Phasen und Neutralleiter dürfen nicht miteinander verwechselt werden Anschluss 1 Die elektrische Versorgung der Kaltwassersätze wird mit einem 3 Leiter Kabel 2 Pole Erde Bezüglich des Kabel Mindestquer schnitts siehe Abschnitt 7 2 2 Das Kabel durch die Kabelschelle am rückseitigen Paneel d...

Page 24: ...vorgese hen a Direkt F direkter Zugang Einstellbar b Mit Passwort C Zugang mit Passwort Werkeinstellung 4 4 1 Parameter der Einheit PARAMETER CODE TYP DEFAULT Serielle Adresse H0 C I Password für Parameter C P5 F 22 4 4 2 Parameter des Sensors PARAMETER CODE TYP DEFAULT Anwahl der Maßeinheit 5 C 0 4 4 3 Parameter des Reglers PARAMETER CODE TYP DEFAULT Differential der Regelung Hysterese 0 0 5 C F ...

Page 25: ...eben der Einheit YBei Verlust von Kältemittel ist erfahrenes und autorisiertes Fach personal zu kontaktieren YDas Schrader Ventil ist nur im Fall eines von der Norm abwei chenden Betriebs der Einheit einzusetzen anderenfalls werden Schä den infolge unkorrekter Kältemittelbefüllung nicht von der Garantie abgedeckt 5 2 Vorbeugende Wartung Für eine stets optimale Effizienz und Zuverlässigkeit des Chi...

Page 26: ...N AN GEGEBENEN GRENZWERT FÜHREN DRUCKSCHALTER DEFEKT ODER UNKORREKT EINGE STELLT DRUCKWÄCHTER ERSETZEN KÜHLMITTELFIL TER VERSTOPFT FILTER ERSETZEN RIPPEN DES KONDENSATORS VERSCHMUTZT RIPPEN DES KONDENSATORS REINIGEN OBERFLÄCHE DES KON DENSATORS BEDECKT BEDECKUNG AN FRONT OBERFLÄCHE DES KONDENSATORS ENTFERNEN WASSER VOLU MENSTROM UNZUREICHEND VOLUMEN STROM DER ZU KÜHLENDEN FLÜSSIGKEIT ER HÖHEN KOMP...

Page 27: ......

Page 28: ... Corsico MI Italy Sede Operativa Hiross Zander Filtration Division Strada Zona Industriale 4 35020 S Angelo di Piove PD Italy tel 39 049 971 2111 fax 39 049 9701911 Web site www parker com hzd e mail technical support hiross parker com A division of Parker Hannifin Corporation ...

Reviews: