PGC, Inc.
Appendix B; SmartPad version 0.503
Steady State & Programmable
November 2005
B-21
Tuning Control Menu
(Steady State and Prog Modes)
Pressing TUNE in the area modification screen will access the tuning control menu. Inside this menu the
user can step through a list of values that can be modified using the PREV (F1) and NEXT (F2) keys. The
top line of the display will indicate the current operating mode. The second line of the display is the
current value that can be accessed. The third line of the display is the current setting for the displayed
value. Enter the new data using the numerical keypad. As in all SmartPad™ data entry, you must fill the
entire field before the information will be accepted.
Press ESC (F4) to exit the tuning control menu and return to the process variable screen.
Label Displayed
Acceptable Data Range
Description
AIR HEATER CONTROL
Control Band
00.00 to 99.99
Defines the proportion (P) portion of
the air temperature control loop.
AIR HEATER CONTROL
Rate
00.00 to 99.99
Defines the rate or integral (I) portion
of the air temperature control loop.
AIR HEATER CONTROL
Derivative
000 to 999
Defines the derivative (D) portion of
the air temperature control loop.
AIR HEATER CONTROL
Manual Adjust
00.00 to 99.99
Defines the air heater output balance
point. In Slow Damper mode the
damper control loop will integrate in
an attempt to control the air
temperature with an output
percentage that is equal to the
manual adjust setting.
AUX HEATER CONTROL
Set Point
00.00 to 99.99
Allows access to the auxiliary heater
control loop set point. * This set point
can be configured to be slaved to the
air set point.
AUX HEATER CONTROL
Actual
00.00 to 99.99
Displays the measured temperature
from the auxiliary RTD.
AUX HEATER CONTROL
Output
00.00 to 99.99
Displays the percentage output
(heater duty cycle) for the auxiliary
control loop
AUX HEATER CONTROL
Control Band
00.00 to 99.99
Defines the proportion (P) portion of
the auxiliary temperature control loop.
AUX HEATER CONTROL
Rate
00.00 to 99.99
Defines the rate or integral (I) portion
of the auxiliary temperature control
loop.
AUX HEATER CONTROL
Derivative
000 to 999
Defines the derivative (D) portion of
the auxiliary temperature control loop.
H2O HEATER CONTROL
Control Band
00.00 to 99.99
Defines the proportion (P) portion of
the water temperature control loop.
H2O HEATER CONTROL
Rate
00.00 to 99.99
Defines the rate or integral (I) portion
of the water temperature control loop.
H2O HEATER CONTROL
Derivative
000 to 999
Defines the derivative (D) portion of
the water temperature control loop.
RH CASCADE CONTROL
Control Band
00.00 to 99.99
Defines the proportion (P) portion of
the Rh cascade control loop.
RH CASCADE CONTROL
Rate
0.000 TO 9.999
Defines the rate or integral (I) portion
of the Rh cascade control loop. This
value will determine the rate of
change for the water set point.
RH CASCADE CONTROL
H2O Hi Limit
00.00 to 99.99 (varies with
hardware)
Defines the maximum water
temperature set point that the system
will allow. This value is hardware
specific.
Summary of Contents for 9354-4250
Page 2: ...PGC Inc Horizontal 500 1000 CFM June 2006 Parameter Generation and Control Inc 2 ...
Page 42: ...PGC Inc Appendix B SmartPad version 0 503 Steady State Programmable November 2005 B 1 ...
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......