PGC, Inc
500-1000 CFM Air Handler
May 2006
Appendix A
A-21
HygroPalm
©
Single-Point Temperature Calibration Procedure
1.)
Install a temperature reference as close as possible to the HygroClip
©
sensor.
2.)
Using a special cable from PGC (Part Number 1609-866), connect the HygroPalm
©
to ACE pc board at the two-pin connector in the upper left-hand corner, labeled DIO.
It is important to note that as long as the HygroPalm
©
is connected to the ACE pc
board, the chamber controller cannot communicate with the HygroClip
©
; therefore,
it is important make the calibration adjustment as quickly as possible.
3.)
Press the HygroPalm
©
down arrow key until the display indicates “PROBE 2”. The
display should indicate the temperature and Rh measured by the HygroClip
©
in the
air handler/chamber. If the display does not indicate the measured temperature and
Rh, check the cable connection
4.)
Press the MENU key. The display will indicate “CALCULATE”
5.)
Press the down arrow
↓
key until the display indicates “ADJUST 1 PT.”
6.)
Press ENTER. The display will indicate “RHS”.
7.)
Press the down arrow key until the display indicates “Temperature”.
8.)
Press ENTER. The display will indicate the current measured temperature. Press the
UP or DOWN ARROW keys until the measured temperature matches the
temperature measured by the reference standard.
9.)
Press ENTER. The display will respond “sure?”. Press ENTER again to enter the
calibration offset.
10.)
The display will respond “wait” until the data written to the HygroClip
©
.
11.)
When “wait” disappears, you can press ENTER to return to the measured value
display screen.
HygroPalm Single-Point Rh Calibration Procedure
1.)
Install an Rh reference as close as possible to the HygroClip
©
sensor.
2.)
Using a special cable from PGC, connect the HygroPalm
©
to the ACE pc board at
the two-pin connector in the upper left-hand corner. It is important to note that as
long as the HygroPalm
©
is connected to the ACE pc board, the chamber controller
cannot communicate with the HygroClip
©
; therefore, it is important make the
calibration adjustment as quickly as possible.
3.)
Press the HygroPalm
©
down arrow key until the display indicates “PROBE 2”. The
display should indicate the temperature and Rh measured by the HygroClip
©
. If the
display does not indicate the measured temperature and Rh, check the cable
connection
4.)
Press the MENU key. The display will indicate “CALCULATE”
5.)
Press the down arrow key until the display indicates “ADJUST 1 PT.”
6.)
Press ENTER. The display will indicate “RHS”.
7.)
Press the down arrow key until the display indicates “Humidity”.
8.)
Press ENTER. The display will indicate the current measured relative humidity.
9.)
Press the UP or DOWN ARROW keys until the measured Rh matches the Rh
measured by the reference standard.
10.)
Press ENTER. The display will respond “sure?”. Press ENTER again to enter the
calibration offset.
11.)
The display will respond “wait” until the data written to the HygroClip
©
. When
“wait” disappears, press ENTER to return to the measured value display screen.
Summary of Contents for 9354-4250
Page 2: ...PGC Inc Horizontal 500 1000 CFM June 2006 Parameter Generation and Control Inc 2 ...
Page 42: ...PGC Inc Appendix B SmartPad version 0 503 Steady State Programmable November 2005 B 1 ...
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......