Latch
The latch facility is designed to be used with intruder detectors fitted with a latch
memory. This feature is very useful when more than one detector has to be wired to a
particular zone as it will show which detectors were triggered if an alarm was
generated. If there has been an alarm and latch memory is used, then when the panel
is reset an LED indication will be given at the relevant detector(s). Resetting of latch
memory requires the panel to be set again for not less than 5 seconds, and then
unset.
Event Log
The Paragon Super control panel incorporates a memory log of the last 18 alarm
events and is accessible to both Master and Limited Users and Engineer. It will
record Fire, Intruder, Personal Attack and Tamper alarms and also show if any of the
6 alarm zones have been triggered or omitted.
The Engineer can set the clearing of the log for either Engineer-only or both Master
User and Engineer.
Auto Rearm
After an alarm the panel will automatically reset itself when the bell timer has expired.
Any zones which still remain triggered at that time will be omitted automatically.
Walk test
The walk test function allows each of the fullset / partset modes to be checked in
order to verify that all the intruder detectors on the alarm system are functioning
correctly. If the panel is set to either Full set or any of the Part-set modes, then only
the non-omitted zones in that particular set mode will activate the walk test chime.
7
7
LIMITED USER FACILITIES
LIMITED USER FACILITIES
Six keys on the keypad are marked with symbols. These symbols are shown below
followed by how they will be referred to in the following text.
Shift
Easy-set
Fire
P.A
Up arrow
Down arrow
1) Full Setting the panel
Enter
Limited User Code (Factory set to 5 6 7 8)
By using this method, maximum volume will be heard.
or
By using this method, Entry / Exit Tone volume will be reduced.
9
9
99.
Panel unset / Day mode.
Fault light is on.
Supply light is on at the control panel.
This indicates a Fuse fault and you should contact
your installation company.
10
10.
Panel unset / Day mode.
Supply light is on and Day light is flashing
This indicates that you have started a command
but not finished the sequence. The panel is waiting
for further commands.
Enter
to escape from command and return to
Day mode.
RDOC280 issue1
RKP
RKP
RKP
RKP
Enter
(Master Code) to exit.
12.
12. Panel unset / Day mode.
Chime light is on, indicating that the panel is
in Chime mode.
Enter
- Chime Light will stay on.
The Paragon Plus will remember its last Set Mode
(Full, 1, 2 or 3). Any zone programmed as
Entry / Exit will chime when triggered.
Enter
to terminate feature and clear
Chime light.
11
11. Panel unset / Day mode.
Chime light is flashing, indicating that the panel
is in Walk-test mode.
Enter
- Chime Light will flash
Set panel to set mode (Full, 1, 2 or 3) that you
wish to test.
Walk Test circuits.