background image

4   Complete Installation Manual   

2.8

ZONE INPUTS

Detection devices such as motion detectors and door contacts are connected to the control panel's zone input terminals labelled Z1, Z2, Z3, Z4
and 

FIRE

 as shown in Figure 8-2: Zone Connections on page 14. Once the zones are connected, the associated zone's parameters must be

defined. For more information, please refer to 

Zone Programming 

on page 5. 

The 

FIRE

 input, which is recognized as zone 6, can be connected as a fire zone or a 24-hour burglary zone. Fire zones must use a 1k

 EOL

resistor. If a line short occurs or if the smoke detector becomes active, whether the system is armed or disarmed, the control panel will generate
an alarm on this zone.

2.9

KEYPAD INSTALLATION

Only the 1686V and the 1686H Spectra Keypads are compatible with the Spectra 1727 control panel. Remove the keypad’s back cover and wire
the 

GRN

YEL

RED

, and 

BLK

 terminals to the corresponding terminals on the control panel as shown in Figure 8-1: PCB Layout on page 13.

2.10

KEYPAD ZONE INSTALLATION

The keypad has one zone input terminal that allows you to connect one motion detector or one door contact directly to the keypad. The keypad
zone is recognized as zone 5. Only one keypad zone can be used per Spectra 1727 control panel. The keypad communicates the status of the
keypad zone to the control panel once the device is connected as shown in Figure 8-1: PCB Layout on page 13 and the zone’s parameters are
defined (see section 3.2). For example, a door contact located at the front door can be wired directly to the input terminal of the keypad instead of
wiring it back to the control panel.

2.11

KEYPAD TAMPER

If the keypad has a tamper switch, the state of the tamper is displayed on zone 5. The control panel cannot differentiate between the open
keypad zone and an open keypad tamper.

Table 1: PGM Events

PGM Event

Description

Exit Delay

The PGM activates during the Exit Delay.

Armed

The PGM activates while the system is armed.

Ready

The PGM activates while the 

READY

 LED is illuminated.

“PG” Key

The PGM activates when the 

PG

 key is pressed and deactivates when the key is pressed again.

Fire Alarm

The PGM activates during a Fire Alarm.

Audible Alarm

The PGM activates during any alarm.

Strobe

The PGM activates while the 

ARM

 LED flashes in alarm.

Entry Delay/Exit Delay/Alarm

The PGM activates during the Entry Delay, the Exit Delay and during an alarm.

Exit Delay/Armed

The PGM activates during the Exit Delay or while the system is armed.

Entry Delay/Alarm

The PGM activates during the Entry Delay or during an alarm.

Regular Armed

The PGM activates while the system is Regular Armed.

Table 2: PGM Options

Option

PGM 1 Events
First Digit

PGM 2 Events
Second Digit

[0]

Exit Delay

Exit Delay

[1]

Armed

Armed

[2]

Ready

Ready

[3]

“PG” Key

“PG” Key

[4]

Fire Alarm

Fire Alarm

[5]

Alarm

Alarm

[6]

Strobe

Strobe

[7]

Entry Delay/Exit Delay/Alarm

Entry Delay/Exit Delay/Alarm

[8]

Exit Delay/Armed

Entry Delay/Alarm

[9]

Regular Arming

Entry Delay/Alarm

Summary of Contents for SPECTRA 1727

Page 1: ...SPECTRA 1727 V1 10 1727 COMPLETE INSTALLATION MANUAL Reference Installation and Programming...

Page 2: ......

Page 3: ...elay 5 Bypass Enabled Zone 5 Stay Zone 5 24 Hour Burglary Zone 5 Instant Zone 5 Follow Zone 5 Fire Zone Programming 6 Zone Speed 6 System Options 6 Exit Delay Timer 6 Entry Delay Timer 6 Bell Cut off...

Page 4: ...which returns programming to STEP 3 1 3 2 MULTIPLE FEATURE SELECT PROGRAMMING METHOD Multiple Feature Select Programming is used in sections 14 15 16 17 18 19 and 20 For sections 14 15 16 17 and 18 e...

Page 5: ...ell output which is protected by a 3A fuse Connect the siren s positive lead to the panel s BELL terminal the negative lead to the relay output NO or NC terminals and connect a wire from the relay s C...

Page 6: ...gure 8 1 PCB Layout on page 13 and the zone s parameters are defined see section 3 2 For example a door contact located at the front door can be wired directly to the input terminal of the keypad inst...

Page 7: ...our Burglary Zone opens whether the system is armed or disarmed the control panel will immediately generate an alarm Select the zones from 1 to 5 to be 24 Hour Zones Zone 6 is already a 24 Hour Zone o...

Page 8: ...apidly and the READY LED will flash during the Exit Delay Key in the desired two digit value from 00 to 99 seconds into section 10 30 seconds by default 4 2 ENTRY DELAY TIMER Section 11 When the syste...

Page 9: ...ill toggle to its opposite state When option 3 is disabled the Bell Relay remains in its opposite state When an alarm occurs it will toggle to its normal state Option 3 OFF The Bell Relay deactivates...

Page 10: ...rt The ARM1 LED will flash when the Exit Delay ends Stay Arming can also be activated using One Touch Arming User Access Codes must have the Stay Arming Option to Stay Arm the system 6 4 FORCE ARMING...

Page 11: ...reviously bypassed zones if any will illuminate 4 Press the ENTER key to accept these entries or press the key s corresponding to the zones you want to change the press ENTER How do use Bypass Recall...

Page 12: ...beep the chime feature has been enabled for that zone If the keypad emits a rejection beep the chime feature has been disabled for the corresponding zone 6 10 KEYPAD MUTING Press and hold the CLEAR b...

Page 13: ...digit code 07 User Code 05 08 User Code 06 09 User Code 07 How Do I Program the PGMs STEP 1 Press the ENTER key STEP 2 Enter the INSTALLER CODE Default 0000 000000 STEP 3 Enter 13 STEP 4 Enter one di...

Page 14: ...17 Follow N N N N N 18 Stay Zone N N N N N Entry Delay Sections 15 16 and 17 must be off for the selected zone Example for an Entry Delay on zone 1 turn key 1 off in sections 15 to 17 Force Zone Progr...

Page 15: ...Spectra 1727 13 8 HARDWARE CONNECTIONS Figure 8 1 PCB Layout...

Page 16: ...14 Complete Installation Manual Figure 8 2 Zone Connections Figure 8 3 PGM Connections...

Page 17: ...ent cannot exceed 200mA for UL installations All outputs are Class 2 or power limited except for the battery terminal The Class 2 and power limited fire alarm circuits shall be installed using CL3 CL3...

Page 18: ...16 Complete Installation Manual Notes...

Page 19: ......

Page 20: ......

Reviews: