Magellan Wireless Expansion Module
19
6.3 Panic Alarm PGM Option (Esprit mode only)
SECTION
[35]
:
OPTION
[2]
When a remote control activates a panic alarm, the MG-RCV3 can either
toggle only the remote control’s enabled PGM output (refer to section 6.1 on
page 18) or toggle the remote control’s enabled PGM output and send a panic
alarm code to the Esprit control panel.
How to set the panic lockout timer.
In step 4 in section 3.2 on page 10:
1. Enter section
[26]
.
2. Enable only one option from
[0]
to
[4]
(refer to Table 6.2 on page 19).
3. Press
[
ENTER
]
.
Table 6.2: Panic Lockout Timer
Key
[0]
ON
= No RF signal lockout on panic alarm (default)
Key
[1]
ON
= 30-second RF signal lockout on panic alarm
Key
[2]
ON
= 60-second RF signal lockout on panic alarm
Key
[3]
ON
= 90-second RF signal lockout on panic alarm
Key
[4]
ON
= 120-second RF signal lockout on panic alarm
How to set the panic alarm PGM option.
In step 4 in section 3.2 on page 10:
1. Enter section
[35]
.
2. Enable or disable option
[2]
.
Option [2]
OFF
= Toggle the enabled PGM output only.
Option [2]
ON
= Toggle the enabled PGM output and send a
panic alarm code.
3. Press
[
ENTER
]
.