September 2022 15
VeriSafe Network Module User Guide, B21176 rev 1 [English]
Rockwell Automation Integration
The
EtherNet/IP
TM
protocol is supplemented by a Add-On Profile (AOP) for easy integration with products
from Rockwell Automation . The AOP supports the Automatic Diagnostics feature .
AOP available in
Studio 5000 Logix Designer V33 .01 or greater
AUTOMATIC DIAGNOSTIC AOP ITEMS
REQUIREMENTS
Logix controller must be V33 or greater
Factory Talk View software must be V12 or greater
CONNECTIVITY STATUS
WORD(2)
Sensor lead status is based on the last completed test . This value will only be updated when a test is
completed with no voltage present .
Table 1
.
Bit
0
1
2
3
Co
nn
ec
tiv
ity
Status
Connected L1
Connected L2
Connected L3
Connected PE GND
Diagnostic Message
0: L1 Sensor lead
disconnected
0: L2 Sensor lead
disconnected
0: L3 Sensor lead
disconnected
0: PE GND Sensor lead
disconnected
1: L1 Sensor lead
connected
1: L2 Sensor lead
connected
1: L3 Sensor lead
connected
1: PE GND Sensor lead
connected
STATUS
DWORD(4)
Status bits associated with the network module and AVT . This value will only be updated when an abcense
of voltage test is completed .
Table 2
.
Bit
0
1
2
3
Status
Battery Warning Indicator AVT Temperature Fault AVT Internal Fault Network Module Fault
0: Battery OK
0: OK
0: OK
0: OK
1: Check battery
(Battery low or not
present)
1: Fault
1: Fault
1: Fault
Diagnostic Message
0: Battery OK
0: AVT temperature OK 0: AVT OK
0: Network module OK
1: Check battery
1: AVT temperature
fault
1: AVT Internal
fault
1: Network module fault