VeriSafe Network Module User Guide, B21176 rev 1 [English] 14
September 2022
MODBUS TCP DATA MODEL IMPLEMENTATION
All values are contained in input registers (offset 30000) .
Data Item
Start Address
Size (16bit words)
End Address
Date/Time
0
4 (uint64)
3
Battery voltage
4
2 (float)
5
Voltage presence
6
1 (uint16)
6
Connectivity status
7
7
Line voltage
L1-G
8
1 (int16)
8
L2-G
9
9
L3-G
10
10
Line voltage peak
L1
11
11
L2
12
12
L3
13
13
Line voltage
L1-L2
14
14
L1-L3
15
15
L2-L3
16
16
Line voltage peak
L1-L2
17
17
L1-L3
18
18
L2-L3
19
19
Temperature
20
1 (int16)
20
Disconnect state
21
1 (uint16)
21
Status
22
2 (uint32)
23
AVT result 1
24
1 (uint16)
24
AVT result 2
25
25
AVT result 1 Date/Time
26
4 (uint64)
29
AVT result 2 Date/Time
30
33
EtherNet/IP
TM
IMPLEMENTATION
The network module supports
EtherNet/IP
TM
. The EDS file can be found on the documentation page of the
web application or by going to panduit .com .