Panduit VeriSafe VS2-NET User Manual Download Page 14

VeriSafe Network Module User Guide, B21176 rev 1 [English]                                           14 

September 2022

MODBUS TCP DATA MODEL IMPLEMENTATION

All values are contained in input registers (offset 30000) .

Data Item

Start Address

Size (16bit words)

End Address

Date/Time

0

4 (uint64)

3

Battery voltage

4

2 (float)

5

Voltage presence

6

1 (uint16)

6

Connectivity status

7

7

Line voltage

L1-G

8

1 (int16)

8

L2-G

9

9

L3-G

10

10

Line voltage peak

L1

11

11

L2

12

12

L3

13

13

Line voltage

L1-L2

14

14

L1-L3

15

15

L2-L3

16

16

Line voltage peak

L1-L2

17

17

L1-L3

18

18

L2-L3

19

19

Temperature

20

1 (int16)

20

Disconnect state

21

1 (uint16)

21

Status

22

2 (uint32)

23

AVT result 1

24

1 (uint16)

24

AVT result 2

25

25

AVT result 1 Date/Time

26

4 (uint64)

29

AVT result 2 Date/Time

30

33

EtherNet/IP

TM

 IMPLEMENTATION

The network module supports 

EtherNet/IP

TM

 . The EDS file can be found on the documentation page of the 

web application or by going to panduit .com .

Summary of Contents for VeriSafe VS2-NET

Page 1: ...Support Page 11 Data Model 12 ModBus TCP Data Model Implementation 14 EtherNet IPTM Implementation 14 Rockwell Automation Integration 15 Automatic Diagnostic AOP Items 15 Troubleshooting 17 Warranty 1...

Page 2: ...plication layout consists of a left sidebar menu and a content area loaded with content cards Sidebar Menu Card Content Area LOGIN On login the user will be directed to the AVT Status page AVT STATUS...

Page 3: ...VT Updated when the user presses the test button and during the wakeup cycle Recommended to replace battery in the AVT when measured below 2 9V 4 Connection Status Status of the connectivity between e...

Page 4: ...age presence Reflects the status of the voltage presence indicators red LEDs on the indicator module and voltage presence contacts on the network module 3 Voltage Measurements Measured peak voltage li...

Page 5: ...quest Data Logs Request data log file from the network module 2 Download Logs CSV Download the data log file to local PC in CSV form 3 Download Filtered Logs CSV If filters are applied download the fi...

Page 6: ...B21176 rev 1 English 6 September 2022 SETTINGS PAGE The settings page allows the user to configure and view the current state of the network module retrieve AVT information check active faults and upd...

Page 7: ...et Time Applies local web browser time to the network module 4 Network Module FW Version Firmware version of the network module 5 Use NTP server Check to enable the use of NTP Network Time Protocol 6...

Page 8: ...alian Korean Spanish Latin America Chinese 18 Restart Restart the network module without saving changes to settings 19 Factory Reset Reset the network module to factory default settings 20 Save Settin...

Page 9: ...ion 21 Faults ID Description 0 Hardware Failure Flash code 2 during boot up 1 Power from the network module to the AVT is over the limit 2 Indicate the network module has been reset to factory default...

Page 10: ...appropriate Update button The firmware update process for both the network module and AVT should take approximately one minute AVT Firmware Update During a firmware update communication between the n...

Page 11: ...odbus TCP communications protocols FIGURe 7 DOCUMENTATION PAGE SUPPORT PAGE Provides contact information and a link to the VeriSafe landing page on www panduit com Queries the AVT and network module f...

Page 12: ...ected Connectivity status Connected status of each sensor lead L1 L2 L3 PE Ground during last test WORD 2 Bit Bit Name 0 Connected L1 1 Connected L2 2 Connected L3 3 Connected PE GND 0 Sensor lead dis...

Page 13: ...following possible bit states to indicate a passed test or the reason for a failed AVT test DWORD 2 Bit 0 1 2 3 4 5 6 7 8 Passed Battery Voltage Low Voltage Exceeded Temperature not in Range Connectiv...

Page 14: ...1 int16 8 L2 G 9 9 L3 G 10 10 Line voltage peak L1 11 11 L2 12 12 L3 13 13 Line voltage L1 L2 14 14 L1 L3 15 15 L2 L3 16 16 Line voltage peak L1 L2 17 17 L1 L3 18 18 L2 L3 19 19 Temperature 20 1 int1...

Page 15: ...2 3 Connectivity Status Connected L1 Connected L2 Connected L3 Connected PE GND Diagnostic Message 0 L1 Sensor lead disconnected 0 L2 Sensor lead disconnected 0 L3 Sensor lead disconnected 0 PE GND S...

Page 16: ...voltage low 1F Voltage exceeded 2F Temperature not in range 3F Connectivity not confirmed 4F Diagnostic Message 0 AVT test failed 0 OK 0 OK 0 OK 0 OK 1 AVT test passed 1 AVT battery low 1 Voltage exce...

Page 17: ...module termination resistor switch positions Move AVT connection cable away from possible noise sources Timeout while communicating with AVT 4 SD card error 5 Contact Panduit for support around SD Car...

Page 18: ...yer whichever is longer 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or servi...

Page 19: ...September 2022 19 VeriSafe Network Module User Guide B21176 rev 1 English...

Page 20: ......

Reviews: