92
29. Tank re-heat temp.
Initial setting: -8°C
-12°C ~ -2°C
Set temp to perform reboil of tank water.
(When boiled by heat pump only, (51°C – Tank re-heat temp) shall become
max temp.)
Setting range is -12°C ~ -2°C
30. Sterilization
Initial setting: 65°C 10min
②
① ③
Set timer to perform sterilization.
1 Set operating day & time. (Weekly timer format)
2 Sterilization temp (55~75°C
If use back-up heater, it is 65°C)
3 Operation time (Time to run sterilization when it reached setting temp
5min ~ 60min)
User shall set whether to use or not to use sterilization mode.
11.3.5 Service Setup
31. Pump maximum speed
Initial setting: Depend on model
Service setup
17:26, Wed
Flow rate
Max. Duty
Operation
88:8 L/min
0xCE
Air Purge
Select
Normally setting is not necessary.
Please adjust when need to reduce the pump sound etc.
Besides that, it has Air Purge function.
32. Pump down
Service setup
17:26, Wed
Pump down:
ON
Confirm
Service setup
17:26, Wed
Pump down:
ON
Confirm
Pump down operation
in progress!
OFF
Operate pump down operation
33. Dry concrete
30°C
1
2
3
4
5
6
35°C
35°C
40°C
40°C
45°C
Stage
Operate concrete curing operation.
Select Edit, set temp for every stage (1~99 1 is for 1 day).
Setting range is 25~55°C
When it is turned ON, dry concrete starts.
When it is 2 zone, it dries both zones.
34. Service contact
Contact-1: Bryan Adams
ABC/ abc
0-9/ Other
A B C D E F G H I J K L M N O P Q R
S T U V W X Y Z
a b c d e f g h i
j k l m n o p q r s t u v w x y z
Select
Enter
Service setup
17:26, Wed
Service contact:
Contact 1
Contact 2
Select
Confirm
Able to set name & tel no. of contact
person when there is breakdown
etc. or client has trouble. (2 items)