126
12.13 Sterilization Mode
Purpose:
-
To sterilize water tank by setting the required boiling temperature.
Remote control setting
-
Days for sterilization function to start can be select.
-
Time of selected day to start sterilization function.
-
Boiling temperature (External heater is 55°C ~ 75°C, Internal heater is 55°C ~ 65°C)
-
Maximum operation time is 5 minutes to 1 hour.
Start condition
-
Tank connection set to “YES” by remote control
-
Sterilization function selects “YES”.
-
Sterilization signal received from remote controller by timer.
-
Tank mode request ON.
Stop condition
-
When boiling timer is completed. Boiling timer (Remote control set maximum operation time) start counting
once tank achieve boiling set temperature
OR
-
After 8 hours of operation since sterilization start.
-
Tank mode request OFF.
Control content:
-
During sterilization function activation time, target tank set temperature will internally change to boiling set
temperature.
-
During sterilization activates, heat pump and heater (external or internal) will operate as normal tank mode to
achieve the boiling set temperature.
-
Sterilization operation will end when stop condition is fulfill.
-
After sterilization is complete, tank set temperature will resume to normal operation.
* Tank temperature may not achieve boiling set temperature if tank heater is select OFF
OR
external compressor
switch.