78
15 Servicing Mode
15.1. Test Run
1. Fill up the boiler tank with water. For details refer to boiler tanks installation instruction and operation instruction.
2. Set ON to the indoor unit and RCCB. Then, for control panel’s operation please refers to air-to-water heatpump’s operation
instruction.
3. For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.2 MPa.
If necessary, adjust the water pump speed accordingly to obtain normal water pressure operating range. If adjust water pump
speed cannot solve the problem, contact your local authorized dealer.
15.2. Proper Pump Down Procedure
1. Make sure the OFF/ON control panel LED is OFF (no operation).
2. Press the “PUMPDW” switch on control panel to begin PUMP DOWN mode. Operate the system in PUMP DOWN mode for
10 ~ 15 minutes.
3. After 10-15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10
°
C)), fully close 2 way valve.
4. After 3 minutes, fully close 3 way valve.
5. Press the “OFF/ON” switch on control panel to stop PUMP DOWN mode.
6. Remove the refrigerant piping.
15.3. How To Adjust Water Flow Rate
• Before adjust the water flow rate, make sure that the total water volume in the installation is 30 litres minimum (07C3 & 09C3),
50 litres minimum (12C6, 14C6 & 16C6).
• The water flow rate can be adjusted with select the water pump speed on the water pump. The default setting is high speed (III).
Adjust it to moderate speed (II) and slow speed (I) if necessary (e.g. reduce the noise of running water).
Below graph shown the external static pressure (kPa) versus water flow rate (l/min).
• Flow rate characteristic of indoor unit is as per above mentioned.
15.4. Expansion Vessel Pre Pressure Checking
• Expansion Vessel with 10L air capacity and initial pressure of 1 bar is installed in this indoor unit.
• Total amount of water in system should be below 200L.
(Note: This amount of water is not include the tank unit volume)
• If total amount of water is over 200L, please add expansion vessel.
• Please keep the installation height difference of system water circuit within 7m.
(Inner volume of same indoor unit is about 5L)
Summary of Contents for WH-SDF07C3E5
Page 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 2 Weekly Timer Setting ...
Page 20: ...20 4 1 3 Setting Up The Special Functions ...
Page 21: ...21 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 22: ...22 5 Dimensions 5 1 Indoor Unit ...
Page 23: ...23 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 24: ...24 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 26: ...26 ...
Page 27: ...27 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...
Page 28: ...28 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 29: ...29 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDF07C3E5 WH SDF09C3E5 ...
Page 30: ...30 8 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 ...
Page 31: ...31 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 32: ...32 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 33: ...33 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDF07C3E5 WH SDF09C3E5 ...
Page 34: ...34 9 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 ...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 36: ...36 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 37: ...37 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 38: ...38 10 1 2 Solar Printed Circuit Board Optional ...
Page 39: ...39 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...
Page 40: ...40 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 41: ...41 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...
Page 42: ...42 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 73: ...73 ...
Page 74: ...74 ...
Page 120: ...120 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 121: ...121 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 138: ...138 20 2 WH UD07CE5 A WH UD09CE5 A ...
Page 139: ...139 ...
Page 142: ...142 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 143: ...143 ...