12.3.4.2. Connecting Requirement
• The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S
sc
is greater than or
equal to 787.57kW (for WH-SDF12C6E5/UD12CE5**, WH-SDF14C6E5/UD14CE5** and WH-SDF16C6E5/UD16CE5**) at the
interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with
a short-circuit power S
sc
greater than or equal to 787.57kW.
• The equipment’s power supply 1 shall be connected to a suitable supply network, with the following maximum permissible
system impedance Z
max
at the interface for models:
WH-SDF12C6E5/UD12CE5**, WH-SDF14C6E5/UD14CE5** and WH-SDF16C6E5/UD16CE5** : 0.244
Ω
Please liaise with supply authority to ensure that the power supply 1 is connected only to a supply of that impedance or less.
• The equipment’s power supply 2 complies with IEC/EN 61000-3-12.
The equipment’s power supply 2 shall be connected to a suitable supply network, with the following maximum permissible
system impedance Z
max
at the interface for models:
WH-SDF12C6E5/UD12CE5**, WH-SDF14C6E5/UD14CE5** and WH-SDF16C6E5/UD16CE5** : 0.236
Ω
Please liaise with supply authority to ensure that the power supply 2 is connected only to a supply of that impedance or less.
• The equipment’s power supply 3 complies with IEC/EN 61000-3-12.
The equipment’s power supply 3 shall be connected to a suitable supply network, with the following maximum permissible
system impedance Z
max
at the interface for models:
WH-SDF12C6E5/UD12CE5**, WH-SDF14C6E5/UD14CE5** and WH-SDF16C6E5/UD16CE5** : 0.464
Ω
Please liaise with supply authority to ensure that the power supply 3 is connected only to a supply of that impedance or less.
Summary of Contents for WH-SDF07C3E5
Page 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 2 Weekly Timer Setting ...
Page 20: ...20 4 1 3 Setting Up The Special Functions ...
Page 21: ...21 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 22: ...22 5 Dimensions 5 1 Indoor Unit ...
Page 23: ...23 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 24: ...24 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 26: ...26 ...
Page 27: ...27 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...
Page 28: ...28 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 29: ...29 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDF07C3E5 WH SDF09C3E5 ...
Page 30: ...30 8 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 ...
Page 31: ...31 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 32: ...32 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 33: ...33 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDF07C3E5 WH SDF09C3E5 ...
Page 34: ...34 9 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 ...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 36: ...36 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 37: ...37 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 38: ...38 10 1 2 Solar Printed Circuit Board Optional ...
Page 39: ...39 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...
Page 40: ...40 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 41: ...41 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...
Page 42: ...42 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 73: ...73 ...
Page 74: ...74 ...
Page 120: ...120 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 121: ...121 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 138: ...138 20 2 WH UD07CE5 A WH UD09CE5 A ...
Page 139: ...139 ...
Page 142: ...142 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 143: ...143 ...