13.1. Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes,
automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the
microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature
shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that
judging the condition according to internal water setting temperature and water outlet temperature.
13.1.1. Internal Water Setting Temperature
Once the operation starts, control panel setting temperature will be taken as base value for temperature shifting processes.
These shifting processes are depending on the Air-to-Water Heatpump settings and the operation environment. The final shifted
value will be used as internal water setting temperature and it is updated continuously whenever the electrical power is supplied
to the unit.
13.1.2. Heating Operation
13.1.2.1. Thermostat control
• Compressor is OFF when Water Outlet Temperature - Internal Water Setting Temperature > 2
°
C for continuously 3 minutes.
• Compressor is ON after waiting for 3 minutes, if the Water Outlet Temperature - Water Inlet Temperature (temperature at
thermostat OFF is triggered) < -3
°
C.
13.1.3. Tank Mode Operation
Control contents:
• 3 ways valve direction
- 3 ways valve switch and fix to tank side.
• Heat Pump Thermostat characteristic
- Water set temperature = tank set temperature or
[55
°
C]
whichever lower.
- Heat Pump Water Outlet set temperature is set to Maximum (55
°
C) at tank mode
i. Case 1
- THERMO OFF TEMP :
1. THERMO OFF TEMP = Water set tempe
[+2
°
C]
.
2. Tank temperature > THERMO OFF TEMP for continuous 3 minutes, heat pump OFF and water pump OFF.
- THERMO ON TEMP :
1. THERMO ON TEMP = Water set tempe
[-3
°
C]
.
2. When detect tank temperature < THERMO ON TEMP, water pump ON for 3 minute then heat pump ON.
- Pump ON when Tank temperature is less than Tank temperature when Heat Pump Thermo Off -
[-3
°
C]
.
Summary of Contents for WH-SDF07C3E5
Page 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 2 Weekly Timer Setting ...
Page 20: ...20 4 1 3 Setting Up The Special Functions ...
Page 21: ...21 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 22: ...22 5 Dimensions 5 1 Indoor Unit ...
Page 23: ...23 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 24: ...24 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 26: ...26 ...
Page 27: ...27 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...
Page 28: ...28 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 29: ...29 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDF07C3E5 WH SDF09C3E5 ...
Page 30: ...30 8 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 ...
Page 31: ...31 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 32: ...32 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 33: ...33 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDF07C3E5 WH SDF09C3E5 ...
Page 34: ...34 9 1 2 WH SDF12C6E5 WH SDF14C6E5 WH SDF16C6E5 ...
Page 35: ...35 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 36: ...36 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 37: ...37 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 38: ...38 10 1 2 Solar Printed Circuit Board Optional ...
Page 39: ...39 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...
Page 40: ...40 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 41: ...41 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...
Page 42: ...42 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 73: ...73 ...
Page 74: ...74 ...
Page 120: ...120 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 121: ...121 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 138: ...138 20 2 WH UD07CE5 A WH UD09CE5 A ...
Page 139: ...139 ...
Page 142: ...142 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 143: ...143 ...